Lunch and Learn 10032018 EVERYTHING YOU ALWAYS WANTED

  • Slides: 35
Download presentation
Lunch and Learn 10/03/2018 EVERYTHING YOU ALWAYS WANTED TO KNOW ABOUT GEN 2 LIQUISHIFT*

Lunch and Learn 10/03/2018 EVERYTHING YOU ALWAYS WANTED TO KNOW ABOUT GEN 2 LIQUISHIFT* *(BUT WERE AFRAID TO ASK) MAW

 • What Is It? • Liqui. Shift is the premier variable rate liquid

• What Is It? • Liqui. Shift is the premier variable rate liquid application system on the market. • Whenever an application scenario calls for onthe-go variable flow due to speed changes (high speed planters or bars) and/or due to rate changes (variable rate prescription application), Liqui. Shift gets the job done accurately, consistently, and with no fuss.

 • How Does It Work? • 2 metering tubes per row • Product

• How Does It Work? • 2 metering tubes per row • Product can flow through: – The small tube (Green) – or The large tube (Orange) – or Both tubes – Accommodating a wide range of variable rates and/or variable speeds

 • Flow starts in small tube. As the flow increases: • When pressure

• Flow starts in small tube. As the flow increases: • When pressure hits the High Setpoint, flow switches to large tube • When pressure hits the High Setpoint, flow switches to both tubes • As flow decreases: • When pressure drops to the Low Setpoint, flow switches from both tubes to large tube • When pressure drops to the Low Setpoint, flow switches to small tube

“B” valves to larger tubes Section Manifold Control Module “A” valves to smaller tubes

“B” valves to larger tubes Section Manifold Control Module “A” valves to smaller tubes Section 4 Section 3 Section 2 Section 1 Pressure transducer IN from flowmeter

Example Generic Drill W/ SS Manifolds Multiple Sections

Example Generic Drill W/ SS Manifolds Multiple Sections

218 -2565 Y 1 Multi. Tube Controller aka Liqui. Shift Controller 8 -pin Deutsch

218 -2565 Y 1 Multi. Tube Controller aka Liqui. Shift Controller 8 -pin Deutsch connector 20 -70 PSI is the default setting

Look At the Lights

Look At the Lights

Multi. Tube Controller aka Liqui. Shift THE LITTLE GUY INSIDE THIS BOX TURNS ON

Multi. Tube Controller aka Liqui. Shift THE LITTLE GUY INSIDE THIS BOX TURNS ON A OR TURNS ON B OR Controller TURNS ON BOTH A & B He waits until he gets a PWM+ Signal on Pin 4 before he goes into action. He reads the voltage from the Pressure Transducer to decide whether he needs A or Both. When he gets the PWM+ Signal he flips on the RED light and one or both of the BLUE lights. He also sends a signal on PIN 6 and/or PIN 7 to the Manifold Controller (for A or Both).

218 -3454 Y 1 Manifold AKA LIQUISHIFT SECTION MODULE LOOK AT Controller THE LIGHTS

218 -3454 Y 1 Manifold AKA LIQUISHIFT SECTION MODULE LOOK AT Controller THE LIGHTS Liqui. Shift® Section Module Lights (Manifold Controller) Section INPUTS (YELLOW) from system controller in cab are on left (from 14 -pin connector) I hope that kid in back gets his stuff together. YELLOW lights show that the system controller is sending the signal for Sections 1 & 2 to be ON. RED light shows 218 -3454 Y 1 that Liqui. Shift control module is YELLOW + RED = BLUE calling for Valve Bank A (small tubes) to be ON. BLUE should match the valves that are ON Section OUTPUTS (BLUE) to section valves are on right (to 23 -pin connector to valves)) BLUE lights show which valves should be ON. BLUE lights show that the Liqui. Shift Manifold Controller is sending the signal for Sections 1 & 2 on Valve Bank A to be ON (1 A & 2 A).

Manual Override Toggle Switches Use for Testing, Flushing, Winterizing, Emergency Operation For Manual Dual

Manual Override Toggle Switches Use for Testing, Flushing, Winterizing, Emergency Operation For Manual Dual Tube Operation: 1. Unplug the 8 -pin Deutsch connector to the Multi. Tube Controller (on the back side of this bracket) 2. Turn on A to use the small tubes or B to use the large tubes, or both A and B to use both tubes.

Liqui. Shift with ISO Sentinel Liqui. Shift Enbl - Check this box if your

Liqui. Shift with ISO Sentinel Liqui. Shift Enbl - Check this box if your system includes a Sure. Fire Liqui. Shift that will be controlled through the Sentinel. Press SAVE when Product Setup is complete - Task Control will restart.

The system can be run as a manual dual tube system by switching from

The system can be run as a manual dual tube system by switching from AUTO to MANUAL and selecting A or Both. High Pressure Up Shift Point is typically 70 PSI. Low Pressure Down Shift Point is typically 20 PSI.

Use a graph like this to see what will happen when you shift from

Use a graph like this to see what will happen when you shift from one tube to another tube.

From Sure. Fire i. Pad Flow Calculator App

From Sure. Fire i. Pad Flow Calculator App

 • No pressure is showing on the display. • What do I do

• No pressure is showing on the display. • What do I do now, 1. Is the pressure sensor plugged in? Where is it plugged in? If it is on Product 2 or Section 7 doc? -12, it will be Sensor 2. If this is the case, be sure your display is showing Pressure Sensor 2. • 2. If it is a liquid pressure sensor on an NH 3 system, it will be Sensor 3. • 3. If it is plugged into the pressure connection on the Section connector on 213 -02 -3764 Y 1 (Trimble), 213 -00 -3765 Y 1 (JD), or 213 -01 -3768 Y 1 (Ag Leader), it will be Pressure 2 (or Aux Pressure). • 4. Is the pressure sensor calibrated? The system must be set for Voltage Based Calibration at 50 mv/PSI. This must be entered while there is no pressure on the sensor. It is best to unplug the sensor while entering the calibration. • 5. Go to Diagnostics > Pressure Sensor (Sensors/Status) >. The 0 PSI voltage should be 0. 00 or 0. 01. The sensor voltage should be reported when there is pressure on the sensor. 1. 0 v is 20 PSI. 2. 0 v is 40 PSI. • 6. If no voltage is being reported, check to see if the green LED light is lit on the end of the sensor. (This can be hard to see in the sun. ) Check for 12 v on the 3 -pin pressure connector (pins B & C—red and black). • 7. A simple pressure signal simulator can be made with a AA or AAA battery. Connect the top of the battery (+) to pin B of the 3 -pin pressure connector. Connect the bottom of the battery (-) to pin C. This should show up as approximately 1. 5 v and 30 psi on the Diagnostics > Readings > Pressure Sensor screen. • 8. If all of the above check out OK, replace the sensor.

Sure. Fire Pressure Signal Simulator (212 -03 -4094 Y 1)— • A great troubleshooting

Sure. Fire Pressure Signal Simulator (212 -03 -4094 Y 1)— • A great troubleshooting tool: • Plug this into the Control Pressure connector. • Turn the dial to increase the voltage. • Watch the display to see the pressure reading (on the Run Screen or on Diagnostics > Readings • Start the system in a Test Mode (such as Calibrate PWM > Pressure Sensors Limits) with the hydraulics turned off. Turn the dial to increase (Sensors/Status)) the voltage to shift from A to B and both A and B. Turn the dial down to shift back.

System shifts back and forth between A and B When the system switches to

System shifts back and forth between A and B When the system switches to the B tubes, the Likely Problem: pressure is too low, so it switches back to A. But, when it switches back to A, the pressure is high enough to switch it back to B. Possible Fixes: 1. Change shifting point jumper from 20 -70 PSI to 20 -80 PSI. 2. Be sure all the A valves are opening when A is ON. 3. Be sure the Manual Override Toggle Switches are OFF (esp. A). 4. Be sure the tube combination is appropriately sized so when it shifts from A to B the pressure will be high enough to keep B ON.

Any questions? Thank you.

Any questions? Thank you.