X618 Digital Public Address and Voice Alarm system
X-618 Digital Public Address and Voice Alarm system TECHNICAL TRAINING
à Honeywell. com Content • Key Features • X 618 Components • X 618 Function • X 618 Connection • X 618 Software 2 Document control number Honeywell Proprietary
à Honeywell. com X 618 Key Features • Full digital system • Full IP Technology Application. Standard Ethernet interface, easy to expand • Decentralize system • Less components • Easy to design • Real time monitoring • Good audio quality 3 Document control number Honeywell Proprietary
à Honeywell. com X-DCS 2000/EN (Work standalone) CD TUNER ZONE 1 LAN X-NPMI X-DCS 2000/EN DCS standalone is a 8 ZONE 8 zones PA/VA system DCS accomplish the operation and monitoring through buttons and LED on the front panel and live paging via the PTT microphone 5 Document control number Honeywell Proprietary
à Honeywell. com X-618 System Topology(One) CD X-NPMI TUNER ZONE 1 FAS PC + Server + Client Ethernet X-DCS 2000/EN CD TUNER PC + Client ZONE 8 ZONE 9 FAS CD TUNER ZONE 17 FAS X-DCS 2000/EN ZONE 16 Audio Line X-DCS 2000/EN 6 Document control number ZONE 24 X-NPMI Loudspeaker Line Cate Network Line Dry Contact Line Honeywell Proprietary
à Honeywell. com X-618 System Topology(Two) CD TUNER FAS CD X-NRI/EN TUNER ZONE 1 FAS X-NPMI Ethernet PC + Server + Client X-DCS 2000/EN CD PC + Client TUNER ZONE 8 ZONE 9 FAS CD TUNER ZONE 1 7 FAS X-DCS 2000/EN ZONE 16 Audio Line X-DCS 2000/EN 7 Document control number ZONE 3 2 X-NPMI Loudspeaker Line Cate Network Line Dry Contact Line Honeywell Proprietary
à Honeywell. com X 618 Components 9 Document control number Honeywell Proprietary
à Honeywell. com Honeywell X-618 Core Components X-DA Series X-DCS 2000/EN Digital Integrated System Manager High Efficiency Power Amplifier X-SMART Management Software X-NPMI Configurable Network Paging Console X-NRI/EN Network Resource Integration Module Xcellent Quality, Xpert Design, Xtra Benefits 10 Document control number Honeywell Proprietary
à Honeywell. com X-618 Components • Digital Integrated System Manager X-DCS 2000/EN • Configurable Network Paging Console X-NPMI • Network Resource Integration Module X-NRI/EN • 1 Channel Class D Amplifier X-DA 1500 EN • 2 Channels Class D Amplifier X-DA 2250 EN • 4 Channels Class D Amplifier X-DA 4125 EN 11 Document control number Honeywell Proprietary
à Honeywell. com X-618 Components Accessories • Push-to-talk Microphone HN-PTT • Integrated Audio Player X-MAP 04 • Noise Detector HN-D 32 N • Volume Controller HN-VC 06/30/60/120 • Cabinet HN-CB 37 • Server PC HN-CP 500 • Input/output Interface Module HN-RTR 12 Document control number Honeywell Proprietary
à Honeywell. com X-DCS 2000/EN Digital Integrated System Manager 13 Document control number Honeywell Proprietary
à Honeywell. com X-DCS 2000/EN Features System capacity up to 250 DCS 2000/EN Simultaneous broadcast 4 audio sources Self-test function Automatic volume control 14 Document control number Amplifier Back up Automatic fault detect Speaker line Monitor • Emergency PTT microphone (Optional HN-PTT) • Remote paging through the X-NPMI via standard Ethernet protocol • 8 supervised zone outputs Open, short, impedance, grounding • 4 auxiliary inputs • 4 ambient noise detector inputs • Built-in loudspeaker that can monitor the zones • Label the zone and source names on the front panel • Internal audio matrix • System expansion through Ethernet Honeywell Proprietary
à Honeywell. com X-DCS 2000/EN Front Panel Zone selection Buttons State Indicator Leds Function Buttons EN-54 Version Audio Source selection button 15 Document control number Honeywell Proprietary
à Honeywell. com X-DCS 2000/EN Rear Panel 1 6 2 3 7 4 8 1. Connect to the power amplifier 2. Recording output 3. Audio inputs 4. 8 trigger inputs 5. 8 trigger outputs(NC、NO) 6. Automatic volume control(AVC) inputs 7. Four 10 M/100 MB switch ports 8. 100 V output terminal 9. 100 V input terminal 10. RJ 45 for modbus connection 16 Document control number 5 10 9 EN-54 Version 24 VDC 220 V ~ Honeywell Proprietary
à Honeywell. com X-DA 2250 EN (Class D Power Amplifier) To DCS 220 V~ Battery Audio input Audio output 17 Document control number Honeywell Proprietary
à Honeywell. com X-NPMI Configurable Network Paging Consol 18 Document control number Honeywell Proprietary
à Honeywell. com X-NPMI LCD touch screen Loudspeaker Operation button Gooseneck microphone socket State indicator light 19 Document control number Honeywell Proprietary
à Honeywell. com X-NPMI Feature: • 4. 3” TFT Touch Panel • 3 Keys for EMG, All Call & Mic X-NPMI Desktop on/off • Emergency Paging X-NPMI+ X-NPMI-R+ HN-PTT 20 Document control number • Connect to Ethernet, up to 20 (Rack Mount) (PTT Mic) NPMI Honeywell Proprietary
à Honeywell. com X-NPMI Feature (Cont. ): • LCD Operation: - Zone paging - Zone group paging - Audio source selection, - Monitoring - Intercom - Password … 21 Document control number Honeywell Proprietary
à Honeywell. com X-NRI/EN Network Resource Integration Module 22 Document control number Honeywell Proprietary
à Honeywell. com X-NRI/EN • When devices group (DCS/NRI/NPMR) has fault, the fault indicator light on the master NRI will glow in yellow and blink. 23 Document control number Features: 4 auxiliary inputs 4 balance inputs with phantom power and gain control Built-in 4 GB SD card for network audio storage 4 ports 10 M/100 MB Ethernet switch 32 monitored dry contact inputs 8 dry contact outputs System capacity up to 8 Main and backup power supply • • Honeywell Proprietary
à Honeywell. com X-NRI/EN Front Panel 1 2 3 1. Power 2. AC Fault 3. DC Fault 4. Running 5. General Fault 6. Network Fault 24 Document control number 4 5 6 EN-54 Version 7 8 9 10 11 7. Emergency 8. Open 9. Short 10. Telephone 11. Audio 1~5 Honeywell Proprietary
à Honeywell. com X-NRI Rear Panel 8 1 9 2 10 3 5 4 7 6 1. Balance inputs 6. Backup power supply 2. Phantom Power/Gain 7. Main power supply 3. 10 M/100 M Network 8. 4 Auxiliary inputs interface 4. 32 Dry contact inputs 5. General Fault outputs 25 Document control number 9. Communication interface 10. RS-485 Honeywell Proprietary
à Honeywell. com X-MAP 04 Integrated Audio Player • • • 26 Document control number Integrated with DVDCD player, USB and SD interface. Support MP 3 file, FM tuner. Two individual DVDCDUSBSD and FM line output. Can play music and applications at 2 zones at the same time. Volume of two line outputs can be adjusted respectively. Three playback modes for DVDCDUSBSD: play single, play all, loop all. FM can each save up 10 channels RS 485 remote control interface Honeywell Proprietary
à Honeywell. com Volume controller • • • Elegant design Support 2 wire, 3 wire, 4 wire, 6 Wire connection ABS Fire Rated housing HN-VC 06 6 W Volume Controller HN-VC 30 30 W Volume Controller HN-VC 60 60 W Volume Controller HN-VC 120 W Volume Controller 27 Document control number Honeywell Proprietary
à Honeywell. com Volume Controller 28 Document control number 2 wire 3 wire 4 wire 6 wire Honeywell Proprietary
à Honeywell. com X 618 Function 31 Document control number Honeywell Proprietary
à Honeywell. com DCS’s Internal structure 32 Document control number Honeywell Proprietary
à Honeywell. com Power Matrix mode Mode A DCS has two working modes, power matrix mode (As above picture) and direct drive mode at next slide At mode A the 8 speaker lines share the power of 1 amplifier Advantage: 1 amplifier can be used by 8 zones Attention: The total power of all the 8 speaker lines should be less than the smallest power amplifier connected to DCS 33 Document control number Honeywell Proprietary
à Honeywell. com Fixed Drive Mode B Each amplifier is fixed to drive two speaker line Advantage: for heavy individual zone load. 34 Document control number Honeywell Proprietary
à Honeywell. com Main and standby amplifier switching function 3 Main + 1 standby amplifier 2 Main + 2 backup amplifier Fully configurable Each DCS can connect up to 4 amplifiers, the standby amplifier can be set to backup main amplifier(1 standby/3 main, 1 standby/2 main, 1 standby/ 1 main, 2 standby/2 main ) The switching function builds in DCS, and no special connection is need. 35 Document control number Honeywell Proprietary
à Honeywell. com Paging and Intercom X-DCS 2000 CD TUNER X-DCS 2000 X-NPMI Ethernet CAT-5 X-DCS 2000 X-NPMI l NPM can manage all DCS 2000 in the system l 255 priorities, task conflict management between NPM by priority. l NPM could activate live paging and emergency paging l Full-duplex intercom between NPMs 37 Document control number Honeywell Proprietary
à Honeywell. com Emergency Broadcast DCS 1 LPI-Mod. Bus DCS 2 …… DCS 6, 9 Dry contacts can activate the voice information in the DCS 2000 flash It can link with the Notifier 3030 and N 6000 system via the modbus card. One Modbus card can max connect 9(3030) or 6(N 6000) pcs of DCS 2000 38 Document control number Honeywell Proprietary
à Honeywell. com Emergency Broadcast DCS 1 LAN X-NRI/EN LPI-Mod. Bus DCS 2 …… DCS 32 X-NRI/EN can interact with the Notifier 3030 and N 6000 system via the modbus card. One X-NRI/EN can max connect 32 pcs of DCS 2000 39 Document control number Honeywell Proprietary
à Honeywell. com X-618 Connect to dual-channel amplifier Audio source input Record output Dry contact signal from FAS Speaker To switch Amplifier channel 1, 2 X-DCS 2000 Main power Backup power Noise detector X-D 2250 Amplifier channel 3,4 Audio line Speaker line Network line FAS linkage line X-D 2250 41 Document control number Honeywell Proprietary
à Honeywell. com X 618 connect to single channel amplifier Audio input Dry contact signal from FAS Record output Speaker To Switch Amplifier Channel 1 X-DCS 2000 Main Power Backup Power Noise Sensor Amplifier Channel 2 X-D 1500 Audio line Speaker line Network line FAS line X-D 1500 42 Document control number Honeywell Proprietary
à Honeywell. com X-SMART System Management Software 43 Document control number Honeywell Proprietary
à Honeywell. com X-SMART System Management Software Functions: • Support to display and operate by map, group & device • Monitor all equipments’ status • Record system operation and fault Log • Record X-NPM paging • Integrated TEXT TO SPEECH interface • Multi Language Interface programmable • Server backup function • Very flexible access level management 44 Document control number Honeywell Proprietary
à Honeywell. com Map View Glance Supported Background Picture format: jpg/jpeg/pvg/bmp/gif/tif 45 Document control number Honeywell Proprietary
à Honeywell. com Log Glance You can check the log file which record the fault time, codes, recovery times, and fault types. 46 Document control number Honeywell Proprietary
à Honeywell. com X-SMART System Management Software For small projects just need one client • X-SPT 900: Mid/small project system management software (include 1 pcs of PA server and 1 pcs of PA client) Max. 20 DCS, 20 audio streams delivered from PC. For big projects need several clients • X-SP 2000: PA Server Max. 250 DCS, 60 audio streams delivered from server. • X-ST 2000: PA client software 48 Document control number Honeywell Proprietary
à Honeywell. com X 618 System Scale • 2, 000 Speaker Lines • 20 Paging Consoles • 1, 000 Audio Outputs for amplifier • 2, 000 Control Contact IN 2, 000 Control Contact OUT by X-DCS 2000/EN • 255 Priorities • MODBUS High Level Interface for Fire alarm panel. 52 Document control number Honeywell Proprietary
à Honeywell. com X 618 System Scale • 32 Audio Inputs (4 per X-NRI/EN) • 40 Audio Streams by X-NRI/EN (5 per X-NRI/EN) • 60 Streams per X-SMART or 20 Streams per X-SMART Med to Small Project System • 256 KB per Audio Stream 53 Document control number Honeywell Proprietary