VAV Minimum Air Selection VAV Example One system

  • Slides: 13
Download presentation
VAV Minimum Air Selection

VAV Minimum Air Selection

VAV Example -One system -Multiple Spaces/Zones - VAV box for each space/zone http: //www.

VAV Example -One system -Multiple Spaces/Zones - VAV box for each space/zone http: //www. trane. com/commercial/library/vol 242/v 24 b 6. asp

VAV System Terms & Equations (you can find them in ASHRAE Standard 62) •

VAV System Terms & Equations (you can find them in ASHRAE Standard 62) • Fraction of minimum outdoor air in space/zone supply air Xi = VOAi / VSAi • Critical space Space with maximum Xi , Z=max(Xi) • Fraction of outdoor air in system supply air X = sum(VOA ) / sum(VSA) • Required Fraction of outdoor air: Y=X/(1+X-Z)

Example Solution Space 1 VSA VOA Xi X Z Y Space 2 Space 3

Example Solution Space 1 VSA VOA Xi X Z Y Space 2 Space 3 Space 4

Examples of sequence of operation

Examples of sequence of operation

HVAC Control Example 1: Economizer (fresh air volume flow rate control) Controlled device is

HVAC Control Example 1: Economizer (fresh air volume flow rate control) Controlled device is damper fresh air - Damper for the air - Valve for the liquids mixing recirc. air T & RH sensors

Economizer % fresh air Fresh air volume flow rate control enthalpy damper Fresh (outdoor)

Economizer % fresh air Fresh air volume flow rate control enthalpy damper Fresh (outdoor) air TOA (h. OA) mixing Recirc. air T & RH sensors 100% Minimum for ventilation

Economizer – cooling regime How to control the fresh air volume flow rate? If

Economizer – cooling regime How to control the fresh air volume flow rate? If TOA < Tset-point → Supply more fresh air than the minimum required The question is how much? % fresh air Open the damper for the fresh air and compare the Troom with the Tset-point. 100% Open till you get the Troom = Tset-point If you have 100% fresh air and your still need cooling use cooling coil. Minimum for ventilation What are the priorities: - Control the dampers and then the cooling coils or - Control the valves of cooling coil and then the dampers ? Defend by SEQUENCE OF OERATION the set of operation which HVAC designer provides to the automatic control engineer

Economizer – cooling regime Example of SEQUENCE OF OERATIONS: If TOA < Tset-point open

Economizer – cooling regime Example of SEQUENCE OF OERATIONS: If TOA < Tset-point open the fresh air damper the maximum position Then, if Tindoor air < Tset-point start closing the cooling coil valve If cooling coil valve is closed and T indoor air < Tset-point start closing the damper till you get T indoor air = T set-point Other variations are possible

HVAC Control Example 2: Dew point control (Relative Humidity control) damper fan fresh filter

HVAC Control Example 2: Dew point control (Relative Humidity control) damper fan fresh filter cooling heating air coil filter mixing T & RH sensors Heat gains Humidity generation We should supply air with lower humidity ratio (w) and lower temperature We either measure Dew Point directly or T & RH sensors substitute dew point sensor

Relative humidity control by cooling coil Cooling Coil Mixture Supply TDP Room Heating coil

Relative humidity control by cooling coil Cooling Coil Mixture Supply TDP Room Heating coil

Relative humidity control by cooling coil (CC) • Cooling coil is controlled by TDP

Relative humidity control by cooling coil (CC) • Cooling coil is controlled by TDP set-point if TDP measured > TDP set-point → send the signal to open more the CC valve if TDP measured < TDP set-point → send the signal to close more the CC valve • Heating coil is controlled by Tair set-point if Tair < Tair set-point → send the signal to open more the heating coil valve if Tair > Tair set-point → send the signal to close more the heating coil valve Control valves Fresh air mixing cooling coil heating coil Tair & TDP sensors

Sequence of operation (PRC environmental chamber) Mixture 3 Set Point (SP) Mixture 1 DPTSP

Sequence of operation (PRC environmental chamber) Mixture 3 Set Point (SP) Mixture 1 DPTSP Mixture 2 Control logic: DBTSP Mixture in zone 1: IF (( TM<TSP) & (DPTM<DPTSP) ) heating and humidifying Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA) decrease humid. Mixture in zone 2: IF ((TM>TSP) & (DPTM<DPTSP) ) cooling and humidifying Cool. coil cont. : IF (TSP<TSA) increase cooling or IF (TSP>TSA) decrease cooling Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA) decrease hum. Mixture in zone 3: IF ((DPTM>DPTSP) ) cooling/dehumidifying and reheatin Cool. coil cont. : IF (DPTSP>DPTSA) increase cooling or IF (DPTSP<DPTSA) decrease cooling Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating