TESYS U COMMANDE PAR MODBUS TSX MICRO MARSEILLE
TESYS U COMMANDE PAR MODBUS TSX MICRO MARSEILLE LE 17 NOVEMBRE 2004 02/2004
PAO 02/2004 2
Liaisons série : Modbus PAO 02/2004 Pré-câblage bobine Module MODBUS Té MODBUS Cordon blindé SCA 62 3
PAO 02/2004 TSX 37 22 TESYS U MAQUETTE LYCEE CHARGE 4
SHEMA CABLAGE PAO 02/2004 5
PAO 02/2004 6
PAO 02/2004 7
PAO 02/2004 8
PAO 02/2004 CONFIGURATION CARTE TSX MICRO 9
PAO 02/2004 1 0
PAO 02/2004 1 1
PAO 02/2004 1 2
PAO 02/2004 MODULE LUCMX 6 BL MULTIFONCTION MARCHE AVANT ECRITURE REGISTRE 1 3
PAO 02/2004 ECRITURE 1 MOT REGISTRE 704 DANS TESYS_U A PARTIR DU MOT MW 200 DU TSX 1 4
LECTURE REGISTRES PAO 02/2004 MODULE LUCMX 12 BL 100% = 3 A 1 5
PAO 02/2004 LECTURE 12 MOTS CONSECUTIFS A PARTIR DU REGISTRE 455 DE TESYS_U RANGES A PARTIR DU MOT MW 100 DANS LE TSX 1 6
PAO 02/2004 EVALUATION DU TEMPS DE TRANSMISSION. A/ THEORIQUE. CALCULS DE TRAMES, NOMBRE OCTETS, TEMPS, ETC. . . B/ PAR PROGRAMMATION. MESURE PAR PROGRAMME , LIMITES. . . C/ PAR OSCILLOSCOPE. MESURES REELLES SUR LA LIGNE DE TRANSMISSION OU SUR ACTIONNEURS. 1 7
A/ Théorique ( Lecture 12 mots ) Évènement 13, 5 ms (9 ms*1, 5) Temps de cycle équipement 1 PAO 02/2004 Compte rendu TC 1 Temps de cycle bus Modbus Temps de cycle équipement 2 13, 5 ms TC 1 TCB TC 2 9, 2 ms TC 2 TCB TC 1 33, 2 ms TSX 37 LIGNE RS 485 9600 Bds 70 ms COM TESYS_U Action CONTACTEUR Temps total # 140 ms 1 8
B/Programme Tâche rapide PAO 02/2004 1 9
C/Oscilloscope PAO 02/2004 Total : # 150 ms 2 0