Talking to SAM - Network Communications for Ne. SSI Terry Krouth Emerson Process Management Ian Verhappen ICE-Pros Inc.
Ne. SSI™: Expanding the Rail Concept Standard Electrical (Digital) Interface “Rail” (HSE) SAM* Linking Device Standard Electrical (Digital) Interface “Rail” (H 1) P Local Indicators V Anyone’s Sensor Anyone’s Actuator Standard Mechanical Interface “Rail” *Sensor/Actuator Manager
Ne. SSI™: Expanding the Rail Concept Standard Electrical (Digital) Interface “Rail” (HSE) Integrated SAM Linking Device Analyzer. etc SAM* LD Standard Electrical (Digital) Interface “Rail” (H 1) P Local Indicators V Anyone’s Sensor Anyone’s Actuator Standard Mechanical Interface “Rail” *Sensor/Actuator Manager
Fieldbus H 1: Connecting the Sensors • Can be used in all Area Classifications and environments – Intrinsically Safe – Full immersion, Dust, … • • • Bi-directional communications Supports Discrete (on/off) and Analog signals Power supplied on cable – Single wire pair to each device • • Proven technology for more than 10 years in the field Global support
Fieldbus H 1 Capabilities • (cont) Control Information Control in the Field – No central controller required for regulatory control • Deterministic – Execute at specific time • Acyclic (without taking system off line) – Maintenance information – Alarms – Configuration changes PID AO AI
Fieldbus Communications Board 1. 5”
Available H 1 Sensors
High Speed Ethernet (HSE) • Controller Level communications protocol based on Standard Commercial Off The Shelf (COTS) Ethernet – 100 MBps normal bandwidth • Encapsulates ALL the functionality of Foundation Fieldbus H 1 protocol – No conversion of data required means full integration in a single control environment • Linking Device used to “bridge” from H 1 to HSE
Additional Manufacturers HSE Linking Devices H 1 Power Supplies H 1 Segments Ethernet Cable …and more are coming
3420
Control in the Field • When developing HSE the Flexible Function Block (FFB) was also created – Two Flavors • Multiple I/O – 8 signals sent as one packet • Flexible – FULLY user configurable and programmable using IEC standard languages • FFB can be programmed by End User or Manufacturer to perform ANY calculation they wish
Flexible Function Block Uses • • Protocol Conversion Logic solving – If this condition respond in this way • Batch recipes – Based on time (i. e. reference signal at 07: 00 every day) • • Advanced Control applications “Portable” to other systems
SAM – Sensor Actuator Manager • • Separate Functionality of SAM across more than one Physical Devices Those functions that cannot be handled by the Linking Device are few leaving “traditional” SAM to serve as an HMI only – Vendor independent HMI possible • OPC to connect with any other system – Full integration with Distributed Control System
Integrated Ne. SSI Business Network Firewall “web” Level 4 Ethernet Historian Level 3 “web” Information Network Ethernet Firewall Control Network Switch Fieldbus HSE SAM Linking Device Fieldbus H 1 Local Indicators Anyone’s Sensor P SAM LD V P Anyone’s Actuator Anyone’s Sensor Fieldbus H 1 V Local Indicators Anyone’s Actuator
Ne. SSI system of the future is here today! Foundation Fieldbus provides this vision in a single fully integrated environment
- Communications network design
- Chapter 3 network protocols and communications
- Ssi definition
- What is ssi
- Ssi bundle
- What is supplemental security income
- Small scale integration (ssi)
- Ssi classification
- Ssi vorteile rechner
- Ex collaboratori ssi
- Ssi circuit
- Autocontrole ssi
- Ssi vs ssdi
- Supplemental security income (ssi)
- Edx720
- Ssdi vs ssi