Standards Approvals Global overview CCC Ro HS Weee
Standards & Approvals Global overview CCC Ro. HS / Weee UL Type E/F – Group UL 508 A © 2002 Eaton Corporation. All rights reserved.
Global Markets & Solutions XT IEC Power Control components have been developed as devices for world markets Test Authorities European Conformance CSA Canada UL U. S. A. China Compulsory Certification China Conformite Europeen IEC / EN 60947 Europe Marine & Off-Shore Shipping Classifications Lolyd’s Register Germanischer Loyd Det Norske Bureau Veritas (DNV) Veritas (BV) Great Britain Germany Norway France
ICD Compliance: Gateway to China • The CCC mark is required for specified products for sale in China • Chinese GB standards are similar to IEC standards • ICD Products requiring the CCC mark are: • Low-voltage motor control components, auxiliary contacts • Pushbuttons, relays above 36 V and below 1000 V • Indicator lights, changeover switches, limit switches • Low-voltage switchgear and control gear assemblies • XT complies with and is marked with CCC
ICD Compliance: Gateway to China • ICD products in process for CCC marking: • S 801 N, R, T, V frames pending • Partial Freedom line pending • 50 mm DP line in process • IT contactors/starters have Certified Body certificates, could be CCC certified by repeating EMC tests in Chinese lab.
Waste Electrical and Electronic Equipment (WEEE) • European Union Directive • Requires the marking and registration of specific electrical & electronic products, primary focus is consumer goods. Recycleable product marking • Requires the collection and reuse or recycling at the end of the product life cycle. • The cost is borne by the producer or importer of the equipment.
Reduction of Hazardous Substances (Ro. HS) • European Union Directive • Restricts the use of several hazardous substances in certain electrical & electronic products. • Implementation date is July 2006 • Restricted substances • • • Hexavalent Chromium PBB & PBDE Mercury Cadmium Lead • XT will conform by end of 2005 • Minor modifications to screw heads and large contactor pcb’s
Meeting UL Type E / Type F with XTPR MMP + XTCE Contactors + Manual Type E Controller plus contactor = = Type F Combination Motor Controller
UL 508 File Table 76. 2
UL Applicatons – Group, Type E & F Standard NEC Panel M M Group Motor Installation Panel SCPD - Circuit Breaker or Fuse Typical Full Voltage Starters MMP Alone (contactor optional) M M UL 508 Type E MMP Panel M M UL 508 Type F CMC Panel Non-Fusible Disconnect (Upstream M M M SCPD needed) MMP+ Line Side Adapter Alone (contactor optional) CMC + Line Side Adapter (contactor included) M M M
Applications: Group Motor Installation l Group Motor Installations n n n l NEC Group Motor rules in Article 430 -53 UL requires that overload and controller be listed for Group Motor applications • Magnetic (short circuit) trip of the MMP provides excellent group motor ratings • Up to 65 k. A maximum available short circuit current XTPB & XTPR devices are UL Listed for Group Installations See Application Manual for more information
UL Distinctions – UL 508 Type E l UL 508 Type E Manual Self Protected Combination Starter (MMP Alone) n n Single Device having integral short circuit protection, a main set of contacts, and motor overload protection Legitimate short circuit protective device & disconnect means for the down stream motor • n The unit clears a fault and does not experience welding of the power poles • n Still requires an upstream feeder short circuit protective device but does not require a dedicated in branch circuit protection or disconnect means Remains fully functional should a short circuit within its ratings occur XTPR 32 & 63 amp are UL Listed as Type E devices
UL Distinctions – UL 508 Type F l UL 508 Type F Combination Motor Controller (CMC) n n CMC consists of a Line Side Adapter, MMP, Wiring Connector Link and XTCE Contactor MMP is a self-protected manual combination starter and provides complete motor branch circuit protection • • • n Contactor switches the motor instead of the MMP • • n Disconnecting Means Short Circuit Protection Overload Protection Contactor is not self-protected Provides long life required for most motor switching applications (millions vs. MMP thousands of operations) Magnetic coil provides for remote control via pushbuttons/PLC High fault Type 2 coordination achieved without oversizing XTFC (15, 32 & 52 A) are UL Listed as Type F devices
Underwriters Laboratory UL 508 A – Control Panels l Who is UL and what role do they play? n n n Independent Testing Company Offering 3 rd Party Certification NEMA Centric, but Going Beyond (c. UL) Consistent with NEC Offer a Variety of Listing Services • • UL 891 – Deadfront Switchboards UL 1058 – Drawout ACBs UL 67 – Panelboards UL 98 – Disconnect Switches UL 489 – Molded Case Circuit Breakers UL 508 A – Control Panels UL 508 E – Self Protecting MMPs UL 508 F – Combination Motor Controllers (CMCs)
Applying the Standard l Short Circuit Protection – Panel Rating n No change to the standard, but…. n Enforcement Begins April 2006 n Customers will have to label with a value n Customers can use fuse table or listed combinations with breakers
Applying the Standard Short Circuit Current Ratings l Requires marking SCCR (Short Circuit Current Rating) on industrial control panels. o l SCCR of the panel is based on one of the following: o o l To provide info for safe installation and inspection of panels based on application: i. e. available fault current to panel. Short circuit rating of a listed and labeled assembly Short circuit rating established using an approved method – UL 508 A 2001 Supplement B is an example Components not to be considered in Short Circuit Current Ratings n Transformers, reactors, dry-type capacitors, resistors, varistors, and voltmeters
Applying the Standard Short Circuit Current Ratings • OEM / Panelbuilder determines SCCR on panel by: o o o Short circuit test of the panel construction Obtain documented tested combinations of components list from a manufacturer who has tested and documented combinations of components, and add these combinations to panelbuilder’s UL procedure. Evaluate panel per UL 508 A, Supplement B (required by 4 -06 if jurisdiction does not adopt 2005 NEC earlier). o o o All components in power circuit must have ratings Panel SCCR is the lowest component short circuit rating o Components or combination of components Supplement B provides tables of components w/o marked short circuit ratings
ICD Action Plan n Developing list of EE components with short circuit values (cat no. , short circuit current at application voltage, UL file info, current limiting yes/no) from UL files. Developing list of EE combination short circuit values (SCPD cat no. , motor control cat no. , short circuit current at application voltage, UL file info) from UL files. Product Line Teams Involved: Power control, Drives, Breakers, Disconnect Switches and Transformers n Provide lists to customers via UL data base and website n Target completion date of August 2005