Smart Let LooseONE Fire Extinction Board Extinction Board
Smart. Let. Loose/ONE Fire Extinction Board
Extinction Board Wiring Smart. Let. Loose/ONE Extinction Board Wiring Smart. Line panel
Extinction Board Wiring Smart. Let. Loose/ONE Smart. Light panel
Initial Wirings Smart. Let. Loose/ONE Initial Wirings Balance MAN-EXT terminals with a 47 kΩ resistance Balance STOP_EXT terminals with a 47 kΩ resistance Balance PRESS terminals with a 47 kΩ resistance
Initial Wirings Smart. Let. Loose/ONE Initial Wirings If terminals aren’t balanced panel displays: Fault 01/03 Open I/O Manual. Extinguish Extin. module Fault 02/03 Open I/O Lock extinguish Extin. module Fault 03/03 Open I/O Pressure switch Extin. module
Initial Wirings Smart. Let. Loose/ONE Initial Wirings Balance PRE-EXT terminals with a 47 kΩ resistance Balance RELEASED terminals with a 47 kΩ resistance
Initial Wirings Smart. Let. Loose/ONE Initial Wirings If terminals aren’t balanced panel displays: Fault 01/02 Open I/O Pre-extinguish Extin. module. Fault Open I/O Released Extin. module 02/02
Electrovalve Wiring Smart. Let. Loose/ONE Electrovalve Wiring 24 V Electrovalve
Electrovalve Wiring Smart. Let. Loose/ONE Electrovalve Wiring If terminals aren’t connected panel displays: Fault Open I/O Valve output Extin. module 01/01
Manual Extinguish Smart. Let. Loose/ONE Manual Extinguish Connect a callpoint or a generic NO contact to have a manual Extinguish input NO contact 15 kΩ resistance 47 kΩ resistance
Stop-Extinguish Smart. Let. Loose/ONE Stop-Extinguish Connect a callpoint or a generic NO contact to have a manual Stop-Extinguish input NO contact 15 kΩ resistance 47 kΩ resistance
Stop-Extinguish Smart. Let. Loose/ONE Stop-Extinguish If fire extinguishant system has been stopped, “R” terminal closes to GND: it can activate a device (eg a led) Device - + +24 V
Pressure Switch Smart. Let. Loose/ONE Pressure Switch A generic NO contact connected to PRESS teminals can be used as: - Supervisory: to monitor gas pressure - From pressure: to confirm that gas cylinders are empty - From flow detector: to confirm that gas has be released NO contact 15 kΩ resistance 47 kΩ resistance
Pre-Extinguish Smart. Let. Loose/ONE Pre-Extinguish PRE-EXT output (terminals 10 -11) is activated on Pre-Extinguish: it can activate some devices 47 kΩ End of Line resistance on the last device
Pre-Extinguish Smart. Let. Loose/ONE Fault 01/01 Short I/O Pre-extinguish Extin. module If panel displays “Short I/O Pre-Extinguish” it will need connect a diode in series (if devices haven’t it) 47 kΩ End of Line resistance on the last device
Released Smart. Let. Loose/ONE Released RELEASED output (terminals 12 -13) is activated when gas extinguishant is released: it can activate some devices. 47 kΩ End of Line resistance on the last device
Released Smart. Let. Loose/ONE Fault Short I/O Released Extin. module 01/01 If panel displays “Short I/O Released” it will need connect a diode in series (if devices haven’t it) 47 kΩ End of Line resistance on the last device
Extinction Board Configuration Smart. Let. Loose/ONE Extinction Board Configuration Extinction Board have to be configured from panel
Extinction Board Configuration Smart. Let. Loose/ONE Smart. Line Panel Enable panel programming phase Extinction Board have to be configured from panel
Extinction Board Configuration Smart. Let. Loose/ONE Smart. Line Panel Control Panel IN PROGRAMMING Ver: 2. 03 01/01/12 17: 45 Settings Disablement Maintenance Programming Configuration Progr. Zone Progr. Output Progr. Timer Extinction Board have to be configured from panel Acquire int. bus Acquire ext. bus Current Devices Extin. module Expansion Ok to execute O O Current Devices Extin. module Expansion Ok to execute 1 O
Extinction Board Configuration Smart. Let. Loose/ONE Smart. Light Panel Enable panel programming phase Extinction Board have to be configured from panel
Extinction Board Configuration Smart. Let. Loose/ONE Smart. Light Panel IN PROGRAMMING Ver: 2. 02 01/01/12 17: 45 Settings Disablement Maintenace Programming Configuration Progr. Point Progr. Zone Progr. Timer Extinction Board have to be configured from panel Loop Bus Extinguish board Smart Level Repeater Ok to continue O O O Extinguish board Smart Level Repeater Ok to continue 1 O O
Programming Smart. Let. Loose/ONE Programming Enable panel programming phase Extinction board is programmed the same way both from Smart. Line panel and from Smart. Light panel
Programming Smart. Let. Loose/ONE Control Panel IN PROGRAMMING Ver: 2. 03 01/01/12 17: 45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish YES: Zone activates extinguish commands NO: least Zone 1: doesn’t activate extinguish At The extinguishant gas releasecommands will activate if at least one of the selected zones go into alarm status At least 2: The extinguishant gas release will activate if at least two of the selected zones go into alarm status All zones: The extinguishant gas release will activate if all selected zones go into alarm status Zone mask: Zone 01 Zone 02 Zone 03 Mode: At least 2 YES YES
Programming Smart. Let. Loose/ONE Control Panel IN PROGRAMMING Ver: 2. 03 01/01/12 17: 45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Do not confirm: extinguishment module doesn’t Zone mask: Zone 01 Zone 02 Zone 03 await confirmation Wait for press. : extinguishment module awaits confirmation from pressure switch Wait for flow: extinguishment module awaits confirmation from flow detector Confirm exting. Do not confirm YES YES
Programming Smart. Let. Loose/ONE Control Panel IN PROGRAMMING Ver: 2. 03 01/01/12 17: 45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Supervisory: PRESS input monitors gas pressure From pressure: PRESS input confirm that gas cylinders are empty From flow det. : PRESS input confirm that gas has be released Zone mask: Zone 01 Zone 02 Zone 03 Pressure switch Supervisory YES YES
Programming Smart. Let. Loose/ONE Control Panel IN PROGRAMMING Ver: 2. 03 01/01/12 17: 45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Pre-extinction time Extinguish time If it is undefined, valve switch will be open until reset Manual Pre-extinction time T. pre-extinct 00 min. 10 sec T. extinguish 00 min. 02 sec Zone mask: Zone 01 Zone 02 Zone 03 YES YES T. extinguish Pressure switch Supervisory T. pre-ext. man 00 min. 00 sec Delay between valve switch activation T. Confirm ext. 00 min. 05 sec and confirmation Pause between one gas discharge and T. Gap discharge another in the event 00 min. 05 sec of non-confirmation Other programming
Advanced Programming Smart. Let. Loose/ONE Advanced Programming - Lock extinguish when the room has open doors Smart. Line Panel
Advanced Programming Smart. Let. Loose/ONE Connect the series of NC doors contact between “I/O” and “-” terminals
Advanced Programming Smart. Let. Loose/ONE “Stop Extinction” “”Swap Alarm-Fault bands” Program I/O Line as “Extinction control Input”
Advanced Programming Smart. Let. Loose/ONE Control Panel Programming from panel IN PROGRAMMING Ver: 2. 03 01/01/12 17: 45 Settings Disablement Maintenance Programming - Lock extinguish when the room has open doors Smart. Line panel Program “I. EXTINGUISH” Configuration Progr. Zone Progr. Output Progr. Timer 01 <Zone 02 <Zone 03 <Zone 04 <Zone 01 02 03 04 10 min. 00 sec. Filter time 30 Detection line I/O line <Zone 01> I. EXTINGUISH Disable exting. NC input NO
Advanced Programming Smart. Let. Loose/ONE Control Panel IN PROGRAMMING Ver: 2. 03 01/01/12 17: 45 Settings Disablement Maintenance Programming - Lock extinguish when the room has open doors Smart. Line panel Program “Lock extinguish” Configurazione Progr. Zone Progr. Uscite Progr. Timer 01 <Zone 02 <Zone 03 <Zone 04 <Zone 01 02 03 04 10 min. 00 sec. Filter time 30 Detection line I/O line <Zone 01> I. EXTINGUISH Lock extinguish NC input NO
Advanced Programming Smart. Let. Loose/ONE Control Panel IN PROGRAMMING Ver: 2. 03 01/01/12 17: 45 Settings Disablement Maintenance Programming - Lock extinguish when the room has open doors Smart. Line panel Program “NC input YES” Configurazione Progr. Zone Progr. Uscite Progr. Timer 01 <Zone 02 <Zone 03 <Zone 04 <Zone 10 min. 00 sec. Filter time 30 Detection line I/O line <Zone 01> I. EXTINGUISH Lock extinguish NC input YES 01 02 03 04