Process Control Methods 1 OpenLoop Control Process control

  • Slides: 38
Download presentation
Process Control Methods 1

Process Control Methods 1

Open-Loop Control • Process control operations are performed automatically by either open-loop or closed-loop

Open-Loop Control • Process control operations are performed automatically by either open-loop or closed-loop systems • Processes controlled only by set-point commands without feedback are open-loop • Open-loop systems are used in applications where simple processes are performed • Open-loop systems are relatively inexpensive 2

Closed-Loop Control • Closed-loop control systems are more effective than openloop systems • With

Closed-Loop Control • Closed-loop control systems are more effective than openloop systems • With the addition of a feedback loop they become self-regulating • Components of a closedloop system include: – The primary element sensor – The controlled variable – The measured variable – The control signal – The final correcting element 3

Process Behavior • The objective of process control is to cause a controlled variable

Process Behavior • The objective of process control is to cause a controlled variable to remain at a constant value at or near some desired set-point • The controlled variable changes because of: – A disturbance appears – Load demands vary – Set points are adjusted 4

Process Behavior Example • Flow through the pipe is the process • Fluid flow

Process Behavior Example • Flow through the pipe is the process • Fluid flow rate is the controlled variable • Valve position is the set point • Demand for the fluid downstream is the load • Variance in upstream pressure is the disturbance 5

Single-Variable Control Loop • Several process variables are controlled at once in a typical

Single-Variable Control Loop • Several process variables are controlled at once in a typical production machine • Usually, only one individual feedback loop is required to control each variable • Single-variable control loops consist of the following elements: – – Measuring device Transducer/transmitter Controller Final Control Element 6

Response Time of the Instrument • All instruments have a time lag - the

Response Time of the Instrument • All instruments have a time lag - the time from when a variable is measured till the corrective action is taken • Factors affecting lag: – Response time of sensor – Time lag of transducer – Distance the signal must travel – Time required for the controller to process – Distance control signal must travel – Time lag of the final correcting element 7

Time Lag • The controlled variable itself may contribute to lag problems because of

Time Lag • The controlled variable itself may contribute to lag problems because of inertia in the variable • Lag due to inertia of the variable is referred to as pure lag • Another factor that affects time lag is dead time this is the elapsed time from when the deviation occurs and corrective action takes place 8

Illustration of Pure Lag 9

Illustration of Pure Lag 9

Selecting a Controller • The controller mode selection is based upon the requirements of

Selecting a Controller • The controller mode selection is based upon the requirements of the process and one of the following control modes will be used: – – On/Off Proportional Integral Derivative 10

On-Off Control • • Used for slow acting operations where lag is unavoidable Final

On-Off Control • • Used for slow acting operations where lag is unavoidable Final correcting element is either fully-on or fully-off The primary drawback of on-off control is the rapid switching of the final control element On-off differential or hysteresis is programmed into the controller • Deadband refers to the differing levels at which a controller switches on and off 11

Continuous Control • On/Off control is acceptable for process where the variable is set

Continuous Control • On/Off control is acceptable for process where the variable is set between two limits • For processes where the variable needs to be kept at particular setpoint level, proportional control is used • Proportional action can be accomplished in two ways: – Time Proportioning Method – Amplitude Proportional Method 12

Time Proportioning • Is a method whereby the output of the controller is continually

Time Proportioning • Is a method whereby the output of the controller is continually switched on and off • On versus off times are varied dependent upon process requirements 13

Amplitude Proportional • Most common technique to produce a proportional signal • The control

Amplitude Proportional • Most common technique to produce a proportional signal • The control signal is proportional in amplitude to the error signal • The signal may be amplified and the amplification may be referred to as proportional gain and proportional band 14

Proportional Gain Comparison Level control at a gain of 1 15

Proportional Gain Comparison Level control at a gain of 1 15

Proportional Gain Comparison (Gain set at 2) 16

Proportional Gain Comparison (Gain set at 2) 16

Proportional Band • Proportional band is defined as the percentage change in the controlled

Proportional Band • Proportional band is defined as the percentage change in the controlled variable that causes the final correcting element to go through 100 percent of its range Controlled Variable % Change PB = Final Correcting Element % Change 17

Integral Control • Because of the introduction of offset in a control process, proportional

Integral Control • Because of the introduction of offset in a control process, proportional control alone is often used in conjunction with Integral control • Offset is the difference between set point and the measured value after corrective action has taken place 18

Reset Action • Integral control is also referred to as reset control as the

Reset Action • Integral control is also referred to as reset control as the set point is continuously reset as long as an error is present • Integral adjustments that affect the output are labeled 3 ways: – Gain - expressed as a whole number – Reset - Expressed in repeats per minute – Integral Time - Expressed in minutes per reset 19

Derivative Mode • • For rapid load changes, the derivative mode is typically used

Derivative Mode • • For rapid load changes, the derivative mode is typically used to prevent oscillation in a process system The derivative mode responds to the rate of change of the error signal rather than its amplitude Derivative mode is never used by itself, but in combination with other modes Derivative action cannot remove offset 20

Control Mode Summary 21

Control Mode Summary 21

Tuning the Controller • Fine-tuning is the process to optimize the controller operation by

Tuning the Controller • Fine-tuning is the process to optimize the controller operation by adjusting the following settings: – Gain setting (proportional mode) – Reset rate (integral mode) – Rate (derivative mode) • Three steps are taken when tuning a systems – Study the control loop – Obtain clearance for tuning procedures – Confirm the correction operation of the system components 22

Trial-and-Error Tuning • Does not use mathematical methods, instead a chart recorder is used

Trial-and-Error Tuning • Does not use mathematical methods, instead a chart recorder is used and several bump tests are made in the proportional and integral modes • Trial-and-error tuning is very time consuming and requires considerable experience on the part of the technician or operator 23

Ziegler-Nichols Tuning Methods • Two formal procedures for tuning control loops: – Continuous cycling

Ziegler-Nichols Tuning Methods • Two formal procedures for tuning control loops: – Continuous cycling method – Reaction curve method 24

Continuous Cycling Method • The continuous cycling method analyzes the process by forcing the

Continuous Cycling Method • The continuous cycling method analyzes the process by forcing the controlled variable to oscillate in even, continuous cycles • The time duration of one cycle is called an ultimate period. The proportional setting that causes the cycling is called the ultimate proportional value • These two values are then used in mathematical formulas to calculate the controller settings 25

Continuous Cycle Calculations • Proportional only controller • Proportional Gain – Kc = Gu

Continuous Cycle Calculations • Proportional only controller • Proportional Gain – Kc = Gu x 0. 5 • KC = proportional gain, • Gu= ultimate gain • Proportional Band – PB = Pbu x 2 • PB = proportional band • Pbu = ultimate proportional band 26

Continuous Cycling Formulas 27

Continuous Cycling Formulas 27

Ziegler-Nichols Reaction Curve Tuning Method • This method avoids the forced oscillations that are

Ziegler-Nichols Reaction Curve Tuning Method • This method avoids the forced oscillations that are found in the continuous cycle tuning method • Cycling should be avoided if the process is hazardous or critical • This method uses step changes and the rate at which the process reacts is recorded • The graph produces three different values used in mathematical calculations to determine the proper controller settings 28

Reaction Curve Tuning Formulas 29

Reaction Curve Tuning Formulas 29

Direct Synthesis Method • • The direct synthesis method uses the same procedures to

Direct Synthesis Method • • The direct synthesis method uses the same procedures to analyze the process times as the Ziegler-Nichols reaction curve method One advantage of this method is that it directly matches (synthesizes) synthesizes the process The first step in this method is perform a bump test and recording the dynamic settling time Depending upon the complexity of the process, one of several dynamic response signals may develop as shown on the right 30

Direct Synthesis Tuning Calculations 31

Direct Synthesis Tuning Calculations 31

Advanced Control Techniques • Some complex manufacturing operations require more precise control than available

Advanced Control Techniques • Some complex manufacturing operations require more precise control than available with PID controllers • Four Techniques frequently used are: – – Cascade control Feed forward control Ratio control Adaptive control 32

Cascade Control • Cascade control systems use a second feedback loop with a separate

Cascade Control • Cascade control systems use a second feedback loop with a separate sensor and controller • Cascade control is effective in overcoming lag in some systems 33

Feedforward Control • Feedforward control measures a variable that enters a process and takes

Feedforward Control • Feedforward control measures a variable that enters a process and takes corrective action if it is affected by a disturbance, reducing or eliminating deviation from the set point 34

Ratio Control • Used in mixing systems where an uncontrolled flow of material (wild

Ratio Control • Used in mixing systems where an uncontrolled flow of material (wild flow) is monitored and used to control the second material which is controlled according to the desired ratio between the two components 35

Adaptive Control • To accommodate a nonlinear process, a microelectronic controller uses software that

Adaptive Control • To accommodate a nonlinear process, a microelectronic controller uses software that has adaptive control capabilities to compensate for nonlinear transducers and sensors 36

END 37

END 37

 • This workforce solution was funded by a grant awarded by the U.

• This workforce solution was funded by a grant awarded by the U. S. Department of Labor’s Employment and Training Administration. The solution was created by the grantee and does not necessarily reflect the official position of the U. S. Department of Labor. The Department of Labor makes not guarantees, warranties, or assurances of any kind, express or implied, with respect to such information, including any information on linked sites and including, but not limited to, accuracy of the information or tis completeness, timeliness, usefulness, adequacy, continued availability, or ownership. This work by Mineral Area College is licensed under the Creative Commons Attribution 4. 0 International License.