Power System Stability Lecture Four Topic Covered Equal
Power System Stability Lecture Four Topic Covered Equal Area Criterion
Re-visit Theoretical Event on Rotor Angle, δ • Events relating rotor angle, δ and power delivered by motor • Events include steady state condition and after fault cleared condition • Rotor angle is focused at the intervals of changes in power delivered
Accelerate area De-accelerate area
Significance of rotor angle changes to stability of motor Notice the position of δC 2 Impact towards rotor angle Influenced creating time, tcr too
Sudden Change in Mechanical Input
Example 1 A generator operates at 50 Hz delivers 1. 0 p. u power to an infinite busbar through a network. A fault occurs which reduces the maximum power transferable to 0. 4 p. u, whereas before fault power was 1. 8 p. u, and post fault power is 1. 3 p. u. By using equal area criterion, determine the critical clearing angle
Given are: Po = 1. 0 p. u = Initial generator output P 1 = 0. 4 p. u = during fault P 2 = 1. 3 p. u = post fault Pm = 1. 8 p. u = pre fault
Convert electrical degree into radian values
Sudden Increase in Power Input Under this application, there a few scenarios considered
Now that during fault with Pe = 0, swing equation becomes: Integrating both side : Integrating again:
Now the corresponding critical clearing time can be determine:
Example 2
Example 3 A 60 Hz synchronous generator having inertia constant H = 5 MJ/MVA and a direct axis transient reactance Xd’ = 0. 3 p. u. is connected to an infinite bus through a purely reactive circuit as shown below. Reactances are marked on the diagram on a common system base. The generator is delivering real power Pe = 0. 8 p. u. and Q = 0. 074 p. u. to an infinite bus at a voltage of V = 1. 0 p. u. a)Determine the transient internal voltage, E’. b)A three phase fault occurs at the middle of one of transmission lines. The fault is cleared, and the faulted line is isolated. Determine the critical clearing angle. c) repeat (a) and (b) with fault occurs at the sending end.
The current flowing into the infinite bus is
The transfer reactance between internal voltage and the infinite bus before fault is:
The transient internal voltage is:
Pre-fault: Since both line are intact when the fault is cleared, the power angle equation at pre-fault:
During fault: The equivalent reactance between generator and the infinite bus
The power-angle curve during fault
Post fault: When fault is cleared the faulted line is isolated. Therefore, the post fault transfer reactance
The power angle curve after fault is
The critical clearing angle
End of Lecture Four
- Slides: 48