ORACLE JERI DB Generation April 27 2004 Coles
ORACLE –JERI DB Generation April 27, 2004 Coles Sibley Jeff Patton SNS Integrated Control System
Overview l MPS Configuration Control » » l Power Supply Apps (design flow) » » l Mode Mask Files Mode Mask Defaults Db Files. substitution files Startup scripts MS Excel (BNL, LANL, LBNL-> SNS) ->. substitutions -> RDB EPICS ->txt (archiver) ->RDB Csv ->Splinefilt->RDB *. txt ->RDB Plans SNS Integrated Control System
Oracle – IOC Application Setup (From MPS but could be any application) l Setup Utility adds or modifies applications to an IOC l (Data can be initially populated by crawling cd. Commands) l Adds directory paths to required file(s) l Each IOC application (i. e. Vx. Stats) has a similar setup window. 1. HW init calls 2. SW Init routines 3. Post IOC init SNS Integrated Control System
Oracle – Hardware setup l Application setup adds hardware, db applications, sequencers, etc. l For example VME board / PCI card info » » » l Hardware address Interrupt vector Hardware version Serial number etc. Custom setup for each type of hardware MPS – Hardware jumpers PMC cards Use Heartbeat? SNS Integrated Control System
Oracle – Channel Setup l Creates “. substitutions” file. Each channel gets instantiated with the template file(s) previously shown. l ADEL, MDEL, SMOO come from manufactures hardware specs and physics requirements l MPS shown below (Software mask jumpers, Mode Masks, etc. ) » Configuration Control and reporting) Data comes from a number of Oracle Tables Need an easy way to get data from RDB table(s) to. substitutions file SNS Integrated Control System
MPS Summary MMP Chain Hardware by IOC File Export options: Chassis IOC MPS Chain Device (From cabling database) Hardware Configuration Channel Configuration Accelerator Readiness Committees accept configuration control procedures (very little paperwork) SNS Integrated Control System
MPS Configuration control reporting MPS configuration changes logged in elog SNS Integrated Control System
MPS Exported files Hardware configuration Substitutions file Expanded db files Startup script Archive config files (From RDB filters) SNS Integrated Control System Created by java script in JERI
Data Flow into EPICS RDB SNS Integrated Control System
Power Supply Application l Initial data came out of excel spreadsheets » Power Supply limits (V and I) » IOC assignments » Channel assignments l Archiver configuration files Initially many sets of files, outdated, wrong. Led to operational errors SNS Integrated Control System
PS / Magnet data from RDB l Power Supply Calibration (from EPICS) l PSC / PSI calibration history l Power supply limits from manufacturer (RDB) l Operational Limits (Ops, magnets, cables, heat waves, etc) l Magnet mapping files l Magnet cycling profiles l SCORE – PS save / restore l Magnetic field set points from accelerator physics model (or golden tune, or last weeks tune, etc) » Alarm limits » MPS trip levels SNS Integrated Control System Status Data is getting into Oracle (Bar code constraints). Substitution files are getting generated
Problems – Future Plans l Problems using an RDB » Controls Group Acceptance (We didn’t do it this way) » Need EPICS or Engineering user interface » ACCL-SRV 1 needs to be mirrored for Oracle development » A lot of overhead to set up, lack of RDB experience » Too many constraints, held up because of missing bar codes l Status and Future Plans » Archiver Configuration, Report generation » ~45 MPS IOC’s and 60 MPS chassis configured » Power Supply IOC Application (testing) » Argonne Collaboration (IRMIS) » PV application locator (IRMIS) » Oracle mirror on ics-accl-srvxx (In progress) » Use RDB for Global System configuration (100’s of IOC’s to manage, will not be able to upgrade all at once) SNS Integrated Control System
SNS Integrated Control System
Signal Management – Import. DB/Templates Startup. cmd imported (crawler App keeps Oracle up to date) Bad signals, duplicates signals, etc flagged. New verses Old comparison Files generated by Oracle go back into the RDB, verifies what is loaded by IOCS. SNS Integrated Control System
- Slides: 14