NYTT KYLSYSTEM MED FLDANDE FRNGARE OCH BUBBLE EXPANSION
NYTT KYLSYSTEM MED FLÖDANDE FÖRÅNGARE OCH BUBBLE EXPANSION VALVE (BXV®) Svenning Ericsson Bubble Expansion. Valve AB EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
GENOMFÖRANDE - LÖSNING TESTRESULTAT BXV-SYSTEM BXV + 245 % 2 W/M K COP +10% KYLEFFEKT + 16% EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
MOTIV FÖR BÄTTRE EFFEKTIVITET /cop • Ca 15% AV DEN GLOBALA EL PRODUKTIONEN ANVÄNDS FÖR ATT KYLA • BXV SYSTEM GER 10 % FÖRBÄTTRING • Ca 200 MILJONER KYLSYSTEM TILLVERKAS/ÅR • CA. = OMSÄTTNING /ÅR 1. 200 MILJARDER KRONOR EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
EFFEKTIVARE KYLA En Inventering 2004 DIREKTEXPANSION FLÖDANDE FÖRÅNGARE TVÅ BAS FAKTORER FÖR VÄRMEÖVERFÖRING TILL KÖLDMEDIER: 1. MASSFLÖDET ÖVER FÖRÅNGAREN. 2. KÖLDMEDIETS GAS/VÄTSKEINNEHÅLL. In forced convective dominant boiling, the heat transfer coefficient is independent of heat flux and dependent on mass flux and quality. Boiling Heat Transfer in Compact Heat Exchangers * T. N. Tran, M. W. Wambsganss, and D. M. France 1 November 14 -18, 1994; EFFYS 2 Dagen 2009 Svenning Ericsson • Problem med oljeåterföring • Elektrisk Pump ”Påtvingad Cirkulation” • Termostatiska expansionsventiler kan ej användas • Potential till högre COP Bubble Expansion Valve AB
GENOMFÖRANDE - NEGATIVA FAKTORER SOM PÅVERKAR NUVARANDE DX SYSTEM? KM KVALITET ? KM MASSFLÖDET ? -RÄTT KM MÄNGD I KONDENSORN - ÖVERHETTNING - OLJA (2, 5 GGR VOL ÖKN) HUVUDFAKTORERNA 1. KM EFFYS 2 Dagen 2009 Svenning Ericsson KVALITET? 2. KM MASSFLÖDE? Bubble Expansion Valve AB
MOTIV – HÖGRE ÅNGTRYCK EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
GENOMFÖRANDE ÅTGÄRDER 1. Den skadliga överhettningen över förångarytorna har eliminerats EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
GENOMFÖRANDE ÅTGÄRDER 2. Köldmediekvalitet= förhållandet mellan gas o vätska i förångaren har optimerats genom att underkyla kondensatet efter kondensorn 1. +MASSFLOW 2. +BETTER QUALLITY BXV 1526 W/m 2 K DX 621 W/m 2 K EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
GENOMFÖRANDE ÅTGÄRDER 3. Massflödesökning cirkulationen av köldmedievätska över förångarytorna har ökat med en effektiv ejektorpump. Effektivare kokning utan stillastående isolerande gasblåsor . EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
GENOMFÖRANDE ÅTGÄRDER 4. Oljeåterföring ifrån förångaren med oljehalt under 1 % (vikt) för att inte isolera förångarytorna med oljehinnan. (Ny koax) EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
GENOMFÖRANDET 5. Rätt fyllning i kondensorn har säkerställts EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
GENOMFÖRANDE - LÖSNING Ny kondensatstyrning har utvecklats BUBBLE EXPANSION VALVE (BXV) EFFYS 2 Dagen 2009 Svenning Ericsson UNDERKYLARE Bubble Expansion Valve AB
GENOMFÖRANDE - LÖSNING MASSFLÖDES ÖKNING NY EJEKTORKONTROLL AV FYLLNING FÖR ”LÄTTSTÖRT KÖLDMEDIA”. + EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
GENOMFÖRANDE – EN KOMPLETT BXV LÖSNING Cp/50 W COMPRESSOR CONDENSER OIL HX DESTILLATOR CONDENSATE FLOW CONTROL SUB COOLER GIVES THE REFRIGERANT SUPERB QUALITY ACCUMULATOR NO SUPERHEAT BRINE OUT EVAPORATOR GRATE MASSFLOW Paralell-flow Cp/250 W BRINE IN EJECTORPUMP EFFYS 2 Dagen 2009 Svenning Ericsson FORCE THE LIQUID THROUGH THE EVAPORATOR Bubble Expansion Valve AB
TEST RESULTAT BXV SYSTEM DX 621 W /m 2 K BXV 1526 W /m 2 K TESTAT AGGREGATETS Växlare B 25 x 24=1, 39 m 2 MEDELDIFFERENSEN MINSKADE 53% EFFYS 2 Dagen 2009 Svenning Ericsson KYLEFFEKTEN ÖKADE 16% Bubble Expansion Valve AB
BXV SYSTEM 1 BUBBLE EXPANSION VALVE KTH 2009 -12 -14
”TRYCKUPPFORDRING” FÖR BRANSCHEN LABTESTER UTFÖRDA AV BXV AB MED SMÅ ROTATIONSMASKINER P 1/P 2 NED TILL 1, 6 GGR (Flytande kondensering) P 1/P 2 UPP TILL 5, 1 GGR TEMP DIFF IN 1, 7 K UT 1, 4 K (40% EG) EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
SUMMERING AV BXV SYSTEMET 1. Ingen överhettning i förångaren 2. Rätt köldmediekvalitet i förångaren 3. Stort massflöde över förångarytorna. 4. Liten oljeinblandning i förångaren. 5. Rätt kondensatkvalitet ut ur kondensorn 6. Mycket energipengar att spara! 1 -6= EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
SUMMERING TACK TERMIA FÖR ATT NI STÄLLDE UPP MED AGGREGAT FÖR TESTERNA! ”DET VÄRMDE” EFFYS 2 Dagen 2009 Svenning Ericsson Bubble Expansion Valve AB
BXV AB EFFYS 2 Dagen 2009 Svenning Ericsson TACK FÖR UPPMÄRKSAMHETEN! Bubble Expansion Valve AB
BXV DX BUBBLE EXPANSION VALVE KTH 2009 -12 -14
Heat Transfer Mechanisms The two fundamental boiling heat transfer mechanisms are force convection and nucleation. In forced convective dominant boiling, the heat transfer coefficient is independent of heat flux and dependent on mass flux and quality; heat transfer increases with increasing mass flux and quality. On the other hand, when nucleation dominates, heat transfer is independent of mass flux and quality and dependent on heat flux and saturation pressure. Boiling Heat Transfer in Compact Heat Exchangers * T. N. Tran, M. W. Wambsganss, and D. M. France 1 Argonne, IL 60439 Prepared for presentation at the 1994 AICh. E Annual Meeting, San Francisco, CA, November 14 -18, 1994; session on Compact Heat Exchangers. BUBBLE EXPANSION VALVE KTH 2009 -12 -14
THIS IS WHERE THE NEW TECNOLGY REALY FITS IN • A. C 50 M/Year • Automotive 120 M/Year • Refrigeration 30 M/Year 23
BUBBLE EXPANSION VALVE KTH 2009 -12 -14
FLYTANDE KONDENSERING BUBBLE EXPANSION VALVE KTH 2009 -12 -14
KORSANDE TEMP BUBBLE EXPANSION VALVE KTH 2009 -12 -14
Korsande växlare BUBBLE EXPANSION VALVE KTH 2009 -12 -14