NICET Fire Alarm Tech Level 1 Practice Test # 7 © Ted Smith 2017

NICET Fire Alarm Tech Level 1 Practice Test # 7 © Ted Smith 2017

Instructions • Be sure to place this presentation in Slide Show Mode if it

Instructions • Be sure to place this presentation in Slide Show Mode if it is not already in that mode before proceeding • The purpose of this drill is to help you improve your skill at finding answers to questions using the applicable fire codes and also to help increase your knowledge of the Fire Alarm codes. • Each slide will contain a question. The question will remain in the screen for a period of 2 minutes. At the end of the two minutes, a notification will sound and the slide will transition to the next slide which will have the correct answer to the question. After 15 seconds the next question will appear and the process will continue. • During the test do not worry about the correct answers when those slide appear. You will be given an opportunity to review the answers with out the time at the end of the test. • Click on the slide to start the timer and begin the test

NFPA 72 1. The primary branch circuit supplying the fire alarm equipment can be

NFPA 72 1. The primary branch circuit supplying the fire alarm equipment can be supplied all of the following EXCEPT which of the following: A. Electric utility B. An engine driven generator if a person trained on its operation is on duty at all times C. An engine driven generator that is monitored by the central station and a runner can respond within 2 hours in the event of a generator shut down D. An engine driven generator arranged for cogeneration with an electric utility if a person trained on its operation is on duty at all times.

Answer • C. • 10. 6. 5. 1. 1

Answer • C. • 10. 6. 5. 1. 1

NFPA 72 2. The fire alarm system circuit disconnecting means shall be permanently identified

NFPA 72 2. The fire alarm system circuit disconnecting means shall be permanently identified as to it purpose. • A. True • B. False

answer • A. True • 10. 6. 5. 2. 2

answer • A. True • 10. 6. 5. 2. 2

NFPA 72 3. The secondary power supply shall automatically provide power to the protected

NFPA 72 3. The secondary power supply shall automatically provide power to the protected premises system within _____ seconds whenever the primary power supply voltage is insufficient for the required system operation. • A. 10 • B. 20 • C. 30 • D. 60

answer • A. 10 • 10. 6. 6. 1

answer • A. 10 • 10. 6. 6. 1

NFPA 72 4. The secondary power supply shall have sufficient capacity to operate the

NFPA 72 4. The secondary power supply shall have sufficient capacity to operate the system under quiescent load ( system operating in normal condition without alarms) for a minimum of 24 hours and at the end of that period, shall be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location of an emergency for _____ minutes. • • A. 2 B. 4 C. 5 D. 10

Answer • C. 5 • 10. 6. 7. 2. 1

Answer • C. 5 • 10. 6. 7. 2. 1

NFPA 72 5. The secondary power supply for Supervising Station Facilities shall consist of

NFPA 72 5. The secondary power supply for Supervising Station Facilities shall consist of below EXCEPT which of the following: A. storage battiers dedicated to the supervising station equipment B. a branch circuit of an automatic starting, engine driven generator C. a branch circuit of multiple engine driven generators at least one of which is automatic starting D. an uniteruptible power supply (UPS)

answer • D. Uninterruptible power supply • 10. 6. 7. 4. 1

answer • D. Uninterruptible power supply • 10. 6. 7. 4. 1

NFPA 72 6. Storage batteries when used as a power supply for a fire

NFPA 72 6. Storage batteries when used as a power supply for a fire alarm system shall be provided with battery charging equipment to recharge the batteries within _______ hours after fully charged batteries have been subject to a single discharge cycle. A. 2 B. 6 C. 24 D. 48

Answer • D. 48 • 10. 6. 10. 3. 2

Answer • D. 48 • 10. 6. 10. 3. 2

NFPA 72 7. Engine driven generators used as a power supply for a fire

NFPA 72 7. Engine driven generators used as a power supply for a fire alarm system shall have enough fuel available in storage sufficient for _______ of testing plus the capacity listed in 10. 6. 7. A. 24 hours B. 48 hours C. 6 months D. 12 months

answer • C. 6 months • 10. 6. 11. 6

answer • C. 6 months • 10. 6. 11. 6

NFPA 72 8. A generator supplied by natural or manufactured gas supplied through reliable

NFPA 72 8. A generator supplied by natural or manufactured gas supplied through reliable utility mains shall not be required to have fuel storage tanks unless they are located in seismic risk zone _______ or greater. A. 1 B. 2 C. 3 D. 4

Answer • C. 3 • 10. 6. 11. 6. 3

Answer • C. 3 • 10. 6. 11. 6. 3

END of QUIz. THE TIME WILL STOP NOW. PLEASE CLICK ON THE SLIDE TO

END of QUIz. THE TIME WILL STOP NOW. PLEASE CLICK ON THE SLIDE TO CONTINUE WITHOUT THE TIMER AND REVIEW EACH QUESTION.

NFPA 72 1. The primary branch circuit supplying the fire alarm equipment can be

NFPA 72 1. The primary branch circuit supplying the fire alarm equipment can be supplied all of the following EXCEPT which of the following: A. Electric utility B. An engine driven generator if a person trained on its operation is on duty at all times C. An engine driven generator that is monitored by the central station and a runner can respond within 2 hours in the event of a generator shut down D. An engine driven generator arranged for cogeneration with an electric utility if a person trained on its operation is on duty at all times.

Answer • C. • 10. 6. 5. 1. 1

Answer • C. • 10. 6. 5. 1. 1

NFPA 72 2. The fire alarm system circuit disconnecting means shall be permanently identified

NFPA 72 2. The fire alarm system circuit disconnecting means shall be permanently identified as to it purpose. • A. True • B. False

answer • A. True • 10. 6. 5. 2. 2

answer • A. True • 10. 6. 5. 2. 2

NFPA 72 3. The secondary power supply shall automatically provide power to the protected

NFPA 72 3. The secondary power supply shall automatically provide power to the protected premises system within _____ seconds whenever the primary power supply voltage is insufficient for the required system operation. • A. 10 • B. 20 • C. 30 • D. 60

answer • A. 10 • 10. 6. 6. 1

answer • A. 10 • 10. 6. 6. 1

NFPA 72 4. The secondary power supply shall have sufficient capacity to operate the

NFPA 72 4. The secondary power supply shall have sufficient capacity to operate the system under quiescent load ( system operating in normal condition without alarms) for a minimum of 24 hours and at the end of that period, shall be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location of an emergency for _____ minutes. • • A. 2 B. 4 C. 5 D. 10

Answer • C. 5 • 10. 6. 7. 2. 1

Answer • C. 5 • 10. 6. 7. 2. 1

NFPA 72 5. The secondary power supply for Supervising Station Facilities shall consist of

NFPA 72 5. The secondary power supply for Supervising Station Facilities shall consist of below EXCEPT which of the following: A. storage battiers dedicated to the supervising station equipment B. a branch circuit of an automatic starting, engine driven generator C. a branch circuit of multiple engine driven generators at least one of which is automatic starting D. an uniteruptible power supply (UPS)

answer • D. Uninterruptible power supply • 10. 6. 7. 4. 1

answer • D. Uninterruptible power supply • 10. 6. 7. 4. 1

NFPA 72 6. Storage batteries when used as a power supply for a fire

NFPA 72 6. Storage batteries when used as a power supply for a fire alarm system shall be provided with battery charging equipment to recharge the batteries within _______ hours after fully charged batteries have been subject to a single discharge cycle. A. 2 B. 6 C. 24 D. 48

Answer • D. 48 • 10. 6. 10. 3. 2

Answer • D. 48 • 10. 6. 10. 3. 2

NFPA 72 7. Engine driven generators used as a power supply for a fire

NFPA 72 7. Engine driven generators used as a power supply for a fire alarm system shall have enough fuel available in storage sufficient for _______ of testing plus the capacity listed in 10. 6. 7. A. 24 hours B. 48 hours C. 6 months D. 12 months

answer • C. 6 months • 10. 6. 11. 6

answer • C. 6 months • 10. 6. 11. 6

NFPA 72 8. A generator supplied by natural or manufactured gas supplied through reliable

NFPA 72 8. A generator supplied by natural or manufactured gas supplied through reliable utility mains shall not be required to have fuel storage tanks unless they are located in seismic risk zone _______ or greater. A. 1 B. 2 C. 3 D. 4

Answer • C. 3 • 10. 6. 11. 6. 3

Answer • C. 3 • 10. 6. 11. 6. 3