Multi-Function control Panel (MFP) AKCmed

Multi-Function control Panel (MFP) AKCmed

Control panel MENU selection ( click on the selected MENU option) • main menu

Control panel MENU selection ( click on the selected MENU option) • main menu • service menu • parameters setting

main menu BACK to menu selection

main menu BACK to menu selection

main menu BACK to menu selection • main MENU is shown on control panel

main menu BACK to menu selection • main MENU is shown on control panel screen • unable intuitive setting of selected functions needed for trouble free operation of the operating room • after accidental touch will screen return to main MENU after 3 seconds • color shown on screen reflects error messages and problems • NOTE: IF NOTHING IS SHOWN – SYSTEM IS STABLE AND WITHOUT ERRORS

BACK to menu selection main menu ( click on the selected button) clock stopwatch

BACK to menu selection main menu ( click on the selected button) clock stopwatch OT lighting ventilation mode full/reduced operation laminar flow unit lighting medical gases control OT temperature setting UPS and ZIS control humidity monitoring in the OT SERVICE

clock BACK to menu selection BACK to main menu

clock BACK to menu selection BACK to main menu

OT lighting • after touching the lighted button will new screen appear • by

OT lighting • after touching the lighted button will new screen appear • by touching on arrow you can adjust lighting intensity • after required intensity is set system switch back to main menu BACK to menu selection BACK to main menu

OT lighting BACK to menu selection BACK to main menu

OT lighting BACK to menu selection BACK to main menu

OT lighting BACK to menu selection BACK to main menu

OT lighting BACK to menu selection BACK to main menu

laminar flow unit lighting • after touch on lighted button will new screen appear

laminar flow unit lighting • after touch on lighted button will new screen appear • by clicking on the arrow you are able to adjust lighting intensity • system will return to main menu once the required lighting intensity is set (same as accidental touch) BACK to menu selection BACK to main menu

laminar flow unit lighting BACK to menu selection BACK to main menu

laminar flow unit lighting BACK to menu selection BACK to main menu

laminar flow unit lighting BACK to menu selection BACK to main menu

laminar flow unit lighting BACK to menu selection BACK to main menu

temperature setting in the OT BACK to menu selection BACK to main menu •

temperature setting in the OT BACK to menu selection BACK to main menu • after touch on lighted button new screen will appear • by touching on arrow you are able to adjust temperature in the operating theatre (required increase/decrease of the temperature in degrees) • after required temperature is set – system will return to main menu • during the temperature setting period is value of the temperature figure white ( delay is caused by ventilation construction and it is not possible to make it faster)

temperature setting in the OT BACK to menu selection BACK to main menu

temperature setting in the OT BACK to menu selection BACK to main menu

temperature setting in the OT BACK to menu selection BACK to main menu

temperature setting in the OT BACK to menu selection BACK to main menu

humidity monitoring in the OT • humidity is only displayed and is not possible

humidity monitoring in the OT • humidity is only displayed and is not possible to be set (ventilation function) BACK to menu selection BACK to main menu

humidity monitoring in the OT BACK to menu selection BACK to main menu

humidity monitoring in the OT BACK to menu selection BACK to main menu

stopwatch • after touch on stopwatch button will system switch to stopwatch menu •

stopwatch • after touch on stopwatch button will system switch to stopwatch menu • three buttons are used – START, STOP, RESET • during the stopwatch function is button lighted in yellow color • to delete the value by using RESET button you will be to do so only after you stop the stopwatch BACK to menu selection BACK to main menu

stopwatch BACK to menu selection BACK to main menu

stopwatch BACK to menu selection BACK to main menu

stopwatch BACK to menu selection BACK to main menu

stopwatch BACK to menu selection BACK to main menu

stopwatch BACK to menu selection BACK to main menu

stopwatch BACK to menu selection BACK to main menu

ventilation mode switching BACK to menu selection BACK to main menu • ventilation is

ventilation mode switching BACK to menu selection BACK to main menu • ventilation is able to be switched between full and reduced mode operation • reduced mode is shown in orange color • after touching the button for switching the ventilation mode will appear window with question, if user like to continue to switch to change the ventilation mode – must confirm its decision (protection against accidental touch) • in case, that selection is not confirmed within 3 seconds will system return to original situation

ventilation mode switching BACK to menu selection BACK to main menu

ventilation mode switching BACK to menu selection BACK to main menu

ventilation mode switching BACK to menu selection BACK to main menu

ventilation mode switching BACK to menu selection BACK to main menu

ventilation mode switching BACK to menu selection BACK to main menu

ventilation mode switching BACK to menu selection BACK to main menu

medical gases control • control panel is monitoring pressure of all medical gases are

medical gases control • control panel is monitoring pressure of all medical gases are set in control panel parameter setting) BACK to menu selection BACK to main menu (types of used • if any gas is in under pressure or overpressure alarm will be activated • alarm will create sound also will be shown on appropriate button of exact gas by red color • in case of alarm is also shown alarm report with advice, how should personnel proceed (this is individually set) • after alarm is confirmed as received (by touching to button with alarm report) will sound alarm go off, button will stay in red color • error message is possible to re-call back anytime after touching on red button of appropriate gas (sound alarm will not operate)

medical gases control BACK to menu selection BACK to main menu

medical gases control BACK to menu selection BACK to main menu

medical gases control BACK to menu selection BACK to main menu

medical gases control BACK to menu selection BACK to main menu

medical gases control BACK to menu selection BACK to main menu

medical gases control BACK to menu selection BACK to main menu

UPS a MIS control BACK to menu selection BACK to main menu • control

UPS a MIS control BACK to menu selection BACK to main menu • control panel is monitoring medical isolated system status • in case of error ( UPS, IC, VIC) alarm will be activated • alarm will create sound as well as is shown in color (yellow, red – depends on type of error) – appropriate MIS button is in color • in case of alarm is also displayed alarm report with advice, how should personnel proceed (individual setting) • after alarm is confirmed (by touching on button with error message) sound alarm will go off but appropriate button of MIS is in red color • alarm report can be re-called back anytime by touching red button MIS (without sound alarm)

UPS a MIS control BACK to menu selection BACK to main menu

UPS a MIS control BACK to menu selection BACK to main menu

UPS a MIS control BACK to menu selection BACK to main menu

UPS a MIS control BACK to menu selection BACK to main menu

UPS and MIS control BACK to menu selection BACK to main menu

UPS and MIS control BACK to menu selection BACK to main menu

service • by using service button you can access to SERVICE MENU BACK to

service • by using service button you can access to SERVICE MENU BACK to menu selection BACK to main menu

service BACK to menu selection BACK to main menu

service BACK to menu selection BACK to main menu

service menu BACK to menu selection BACK to main menu

service menu BACK to menu selection BACK to main menu

service menu BACK to menu selection BACK to main menu • service menu can

service menu BACK to menu selection BACK to main menu • service menu can be accessed by touching on SERVICE button • if someone touch accidently button SERVICE the system will return back to main menu after 3 seconds • if we are in service menu we can return back after touching button BACK • in this menu is possible to test IC and VIC, set time and date, shown alarm history and to find status of some control panel parts • by touching button PARAMETERS SETTING you can access to another menu

service menu BACK to menu selection BACK to main menu IC and VIC circuits

service menu BACK to menu selection BACK to main menu IC and VIC circuits date and time adjustment alarm history other error reports PARAMETER SETTINGS

IC and VIC testing BACK tu menu selection BACK service menu • IC and

IC and VIC testing BACK tu menu selection BACK service menu • IC and VIC testing buttons able to do regular control of isolated status • after touching button you can hear sound signal during the testing period • if test will be successful, there will be button lighted in green color, if test was not successfully completed, the button will be lighted in red color • result of the test is also stored in so called history alarm section

IC and VIC testing BACK to menu selection BACK service menu

IC and VIC testing BACK to menu selection BACK service menu

IC and VIC testing BACK to menu selection BACK service menu

IC and VIC testing BACK to menu selection BACK service menu

IC and VIC testing BACK to menu selection BACK service menu

IC and VIC testing BACK to menu selection BACK service menu

alarm history display BACK to menu selection BACK service menu • by pressing button

alarm history display BACK to menu selection BACK service menu • by pressing button – ALARM HISTORY whole alarm history and testing of medical isolated systems will be displayed • in menu you can move by using arrows in left part of the screen • by pressing button BACK you will return to service menu

alarm history display BACK to menu selection BACK service menu

alarm history display BACK to menu selection BACK service menu

History alarm display BACK to menu selection BACK service menu

History alarm display BACK to menu selection BACK service menu

date and time settings • after touch on the button „Date and time settings“

date and time settings • after touch on the button „Date and time settings“ we can set up required values • thanks to button BACK we can return to service menu BACK to menu selection BACK service menu

date and time settings BACK to menu selection BACK service menu

date and time settings BACK to menu selection BACK service menu

other error reports • buttons show if all functions are in order (green color)

other error reports • buttons show if all functions are in order (green color) • in case of error are buttons in red color, it is necessary to call service after problem is found • red color buttons are not showing critical errors, but errors which you are unable to find by other way BACK to menu selection BACK service menu

other error report BACK to menu selection BACK service menu

other error report BACK to menu selection BACK service menu

parameters setting BACK to menu selection BACK service menu • by using button PARAMETERS

parameters setting BACK to menu selection BACK service menu • by using button PARAMETERS SETTING we can access to other menu, which is selected for setting of individual parameters of the control panel

parameters setting BACK to menu selection BACK service menu

parameters setting BACK to menu selection BACK service menu

parameters setting BACK to menu selection BACK service menu

parameters setting BACK to menu selection BACK service menu

parameters setting BACK to menu selection BACK service menu • menu parameter setting is

parameters setting BACK to menu selection BACK service menu • menu parameter setting is accessible from service menu once password is entered • in this menu you are able to set up all the functions of control panel • also functions not mentioned in this presentation are accessible (operating light control, LCD TV control, monitor control, CODE BLUE, etc. ) • 200 alternatives of different parameters can be set • this menu is normally not accessible by customer

parameters setting BACK to menu selection BACK service menu

parameters setting BACK to menu selection BACK service menu