Modern Control Systems MCS Lecture6 7 Lead Compensation

  • Slides: 54
Download presentation
Modern Control Systems (MCS) Lecture-6 -7 Lead Compensation Dr. Imtiaz Hussain Assistant Professor email:

Modern Control Systems (MCS) Lecture-6 -7 Lead Compensation Dr. Imtiaz Hussain Assistant Professor email: imtiaz. hussain@faculty. muet. edu. pk URL : http: //imtiazhussainkalwar. weebly. com/ 1

Lecture Outline • Introduction to Lead Compensation • Electronic Lead Compensator • Electrical Lead

Lecture Outline • Introduction to Lead Compensation • Electronic Lead Compensator • Electrical Lead Compensator • Mechanical Lead Compensator 2

Lead Compensation • Lead Compensation essentially yields an appreciable improvement in transient response and

Lead Compensation • Lead Compensation essentially yields an appreciable improvement in transient response and a small change in steady state accuracy. • There are many ways to realize lead compensators and lag compensators, such as electronic networks using operational amplifiers, electrical RC networks, and mechanical spring-dashpot systems. 3

Lead Compensation • Generally Lead compensators are represented by following transfer function • or

Lead Compensation • Generally Lead compensators are represented by following transfer function • or 4

Lead Compensation 5

Lead Compensation 5

Electronic Lead Compensator • Following figure shows an electronic lead compensator using operational amplifiers.

Electronic Lead Compensator • Following figure shows an electronic lead compensator using operational amplifiers. 6

Electronic Lead Compensator • 7

Electronic Lead Compensator • 7

Electronic Lead Compensator • Pole-zero Configuration of Lead Compensator 8

Electronic Lead Compensator • Pole-zero Configuration of Lead Compensator 8

Lead Compensation Techniques Based on the Root-Locus Approach. • The root-locus approach to design

Lead Compensation Techniques Based on the Root-Locus Approach. • The root-locus approach to design is very powerful when the specifications are given in terms of timedomain quantities, such as – – – damping ratio undamped natural frequency desired dominant closed-loop poles maximum overshoot rise time settling time. 9

Lead Compensation Techniques Based on the Root-Locus Approach. • The procedures for designing a

Lead Compensation Techniques Based on the Root-Locus Approach. • The procedures for designing a lead compensator by the root-locus method may be stated as follows: – Step-1: Analyze the given system via root locus. 10

Step-2 • From the performance specifications, determine the desired location for the dominant closed-loop

Step-2 • From the performance specifications, determine the desired location for the dominant closed-loop poles. 11

Step-3 • From the root-locus plot of the uncompensated system (original system), ascertain whether

Step-3 • From the root-locus plot of the uncompensated system (original system), ascertain whether or not the gain adjustment alone can yield the desired closed loop poles. • If not, calculate the angle deficiency. • This angle must be contributed by the lead compensator if the new root locus is to pass through the desired locations for the dominant closed-loop poles. 12

Step-4 • Assume the Lead Compensator to be: • Where α and T are

Step-4 • Assume the Lead Compensator to be: • Where α and T are determined from the angle deficiency. • Kc is determined from the requirement of the open-loop gain. 13

Step-5 • If static error constants are not specified, determine the location of the

Step-5 • If static error constants are not specified, determine the location of the pole and zero of the lead compensator so that the lead compensator will contribute the necessary angle. • If no other requirements are imposed on the system, try to make the value of α as large as possible. • A larger value of α generally results in a larger value of Kv, which is desirable. • Larger value of α will produce a larger value of Kv and in most cases, the larger the Kv is, the better the system performance. 14

Step-6 • Determine the value of Kc of the lead compensator from the magnitude

Step-6 • Determine the value of Kc of the lead compensator from the magnitude condition. 15

Final Design check • Once a compensator has been designed, check to see whether

Final Design check • Once a compensator has been designed, check to see whether all performance specifications have been met. • If the compensated system does not meet the performance specifications, then repeat the design procedure by adjusting the compensator pole and zero until all such specifications are met. 16

Final Design check • If the selected dominant closed-loop poles are not really dominant,

Final Design check • If the selected dominant closed-loop poles are not really dominant, or if the selected dominant closed-loop poles do not yield the desired result, it will be necessary to modify the location of the pair of such selected dominant closed-loop poles. 17

Example-1 • Consider the position control system shown in following figure. • It is

Example-1 • Consider the position control system shown in following figure. • It is desired to design an Electronic lead compensator Gc(s) so that the dominant closed poles have the damping ratio 0. 5 and undamped natural frequency 3 rad/sec. 18

Step-1 (Example-1) • Draw the root Locus plot of the given system. • The

Step-1 (Example-1) • Draw the root Locus plot of the given system. • The closed loop transfer function of the given system is: • The closed loop poles are 19

Step-1 (Example-1) • Determine the characteristics of given system using root loci. • The

Step-1 (Example-1) • Determine the characteristics of given system using root loci. • The damping ratio of the closed-loop poles is 0. 158. • The undamped natural frequency of the closed-loop poles is 3. 1623 rad/sec. • Because the damping ratio is small, this system will have a large overshoot in the step response and is not desirable. 20

Step-2 (Example-1) • From the performance specifications, determine the desired location for the dominant

Step-2 (Example-1) • From the performance specifications, determine the desired location for the dominant closed-loop poles. • Desired performance Specifications are: § It is desired to have damping ratio 0. 5 and undamped natural frequency 3 rad/sec. 21

Step-2 (Example-1) • Alternatively desired location of closed loop poles can also be determined

Step-2 (Example-1) • Alternatively desired location of closed loop poles can also be determined graphically § Desired ωn= 3 rad/sec § Desired damping ratio= 0. 5 Desired Closed Loop Pole 22

Step-3 (Exampl-1) • From the root-locus plot of the uncompensated system ascertain whether or

Step-3 (Exampl-1) • From the root-locus plot of the uncompensated system ascertain whether or not the gain adjustment alone can yield the desired closed loop poles. Desired Closed Loop Pole 23

Step-3 (Exampl-1) • If not, calculate the angle deficiency. • To calculate the angle

Step-3 (Exampl-1) • If not, calculate the angle deficiency. • To calculate the angle of deficiency apply Angle Condition at desired closed loop pole. Desired Closed Loop Pole -2 -1 100. 8 o -2 120 o -1 24

Step-3 (Exampl-1) • Alternatively angle of deficiency can be calculated as. Where are desired

Step-3 (Exampl-1) • Alternatively angle of deficiency can be calculated as. Where are desired closed loop poles 25

Step-4 (Exampl-1) • This angle must be contributed by the lead compensator if the

Step-4 (Exampl-1) • This angle must be contributed by the lead compensator if the new root locus is to pass through the desired locations for the dominant closed-loop poles. • Note that the solution to such a problem is not unique. There are infinitely many solutions. 26

Step-5 (Exampl-1) Solution-1 • Solution-1 – If we choose the zero of the lead

Step-5 (Exampl-1) Solution-1 • Solution-1 – If we choose the zero of the lead compensator at s = -1 so that it will cancel the plant pole at s =-1, then the compensator pole must be located at s =-3. 27

Step-5 (Example-1) Solution-1 • If static error constants are not specified, determine the location

Step-5 (Example-1) Solution-1 • If static error constants are not specified, determine the location of the pole and zero of the lead compensator so that the lead compensator will contribute the necessary angle. 28

Step-5 (Example-1) Solution-1 • The pole and zero of compensator are determined as 29

Step-5 (Example-1) Solution-1 • The pole and zero of compensator are determined as 29

Step-6 (Example-1) Solution-1 • The Value of Kc can be determined using magnitude condition.

Step-6 (Example-1) Solution-1 • The Value of Kc can be determined using magnitude condition. 30

Final Design Check Solution-1 • The open loop transfer function of the designed system

Final Design Check Solution-1 • The open loop transfer function of the designed system then becomes • The closed loop transfer function of compensated system becomes. 31

Final Design Check Solution-1 32

Final Design Check Solution-1 32

Final Design Check Solution-1 • The static velocity error constant for original system is

Final Design Check Solution-1 • The static velocity error constant for original system is obtained as follows. • The steady state error is then calculated as 33

Final Design Check Solution-1 34

Final Design Check Solution-1 34

Final Design Check Solution-1 • The static velocity error constant for the compensated system

Final Design Check Solution-1 • The static velocity error constant for the compensated system can be calculated as • The steady state error is then calculated as 35

Step-5 (Exampl-1) Solution-2 • Solution-2 -2 -1 90 o 49. 2 o -3 -2

Step-5 (Exampl-1) Solution-2 • Solution-2 -2 -1 90 o 49. 2 o -3 -2 -1 36

Step-5 (Exampl-1) Solution-2 • Solution-2 -2 -1 90 o 49. 2 o -3 -2

Step-5 (Exampl-1) Solution-2 • Solution-2 -2 -1 90 o 49. 2 o -3 -2 -1 37

Step-5 (Example-1) Solution-3 • If no other requirements are imposed on the system, try

Step-5 (Example-1) Solution-3 • If no other requirements are imposed on the system, try to make the value of α as large as possible. A larger value of α generally results in a larger value of Kv, which is desirable. • Procedure to obtain a largest possible value for α. – First, draw a horizontal line passing through point P, the desired location for one of the dominant closed-loop poles. This is shown as line PA in following figure. – Draw also a line connecting point P and the origin O. P A -2 -1 -3 -2 -1 O 38

Step-5 (Example-1) Solution-3 • Bisect the angle between the lines PA and PO, as

Step-5 (Example-1) Solution-3 • Bisect the angle between the lines PA and PO, as shown in following figure. P A -2 -1 -3 -2 -1 O 39

Step-5 (Example-1) Solution-3 • P A -2 -1 C -3 B -2 -1 O

Step-5 (Example-1) Solution-3 • P A -2 -1 C -3 B -2 -1 O D 40

Step-5 (Example-1) Solution-3 • The lead compensator has zero at s=– 1. 9432 and

Step-5 (Example-1) Solution-3 • The lead compensator has zero at s=– 1. 9432 and pole at s=– 4. 6458. P A -2 -1 C -3 B -2 -1 O D • Thus, Gc(s) can be given as 41

Step-5 (Example-1) Solution-3 • 42

Step-5 (Example-1) Solution-3 • 42

Step-6 (Example-1) Solution-3 • Determine the value of Kc of the lead compensator from

Step-6 (Example-1) Solution-3 • Determine the value of Kc of the lead compensator from the magnitude condition. 43

Step-6 (Example-1) Solution-3 • The Kc is calculated as • Hence, the lead compensator

Step-6 (Example-1) Solution-3 • The Kc is calculated as • Hence, the lead compensator Gc(s) just designed is given by 44

Final Design Check Solution-3 Desired Closed Loop Pole Uncompensated System Compensated System 45

Final Design Check Solution-3 Desired Closed Loop Pole Uncompensated System Compensated System 45

Final Design Check Solution-3 • It is worthwhile to check the static velocity error

Final Design Check Solution-3 • It is worthwhile to check the static velocity error constant Kv for the system just designed. • Steady state error is 46

Final Design Check Solution-3 47

Final Design Check Solution-3 47

Final Design Check Solution-1 Solution-3 48

Final Design Check Solution-1 Solution-3 48

Mechanical Lead Compensator • Figure shows the mechanical lead compensator. • Equations are obtained

Mechanical Lead Compensator • Figure shows the mechanical lead compensator. • Equations are obtained as • Taking Laplace transform of these equations assuming zero initial conditions and eliminating Y(s), we obtain 49

Mechanical Lead Compensator • By defining • We obtain 50

Mechanical Lead Compensator • By defining • We obtain 50

Exampl-2 • Design a mechanical lead compensator following system. • The damping ratio of

Exampl-2 • Design a mechanical lead compensator following system. • The damping ratio of closed loop poles is 0. 5 and natural undamped frequency 2 rad/sec. It is desired to modify the closed loop poles so that natural undamped frequency becomes 4 rad/sec without changing the damping ratio. 51

Electrical Lead Compensator 52

Electrical Lead Compensator 52

Example-3 • Consider the model of space vehicle control system depicted in following figure.

Example-3 • Consider the model of space vehicle control system depicted in following figure. • Design an Electrical lead compensator such that the damping ratio and natural undamped frequency of dominant closed loop poles are 0. 5 and 2 rad/sec. 53

To download this lecture visit http: //imtiazhussainkalwar. weebly. com/ END OF LECTURES-6 -7 54