lindab we simplify construction Professor Plus Indoor Climate
lindab | we simplify construction Professor Plus Indoor Climate Solutions NEW! For a PLUS on capacity
lindab | we simplify construction Professor An old game changer • The original Professor beam – Well known and valued
lindab | we simplify construction Professor Plus The new standard • The new Professor Plus – All the Professor features plus some more…
lindab | we simplify construction Professor Plus Types • Width – 60 mm as type I-60 and F-60. • Length – 1. 2 m up to 3. 6 m in steps of 0. 6 m • Type F-60 – Has no updated face place • Other types for special ceilings are also available F. E. : – Clip in Universal (X-60) – Clip in Metal (K-60) – Clip in DG (J-60) – Clip in T 24 (Y-60) – Clip in T 15 (Z-60) – Clip in L (L-60) • Other ceiling types/versions – Require implementing of new drawing first Installation instruction
lindab | we simplify construction Cooling capacities Professor Plus • Professor 1. 8 m, 15 l/s, 40 Pa – Cooling capacity = 528 W • Professor Plus 1. 8 m, 15 l/s, 40 Pa – Cooling capacity = 619 W (+17 %) • Professor 2. 4 m, 20 l/s, 60 Pa – Cooling capacity = 810 W • Professor Plus 2. 4 m, 20 l/s, 60 Pa – Cooling capacity = 905 W (+12 %) • Professor 3. 6 m, 40 l/s, 80 Pa – Cooling capacity = 1493 W • Professor Plus 3. 6 m, 40 l/s, 80 Pa – Cooling capacity = 1711 W (+15 %) Room temp: 25°C Inlet air: 18°C Water in-out: 14 -17°C
lindab | we simplify construction Professor vs Professor Plus PLT 60 Pa 80 Pa 100 Pa 120 Pa Prof. Plus l/[s m] qa/Lact qa/Lact 5 24, 1 25 10 31, 3 36, 6 33, 8 38, 2 34, 2 39, 4 40, 5 15 35, 4 44, 7 37 46 38, 3 47, 7 48, 5 20 38, 4 47, 5 39, 9 50, 6 41, 2 53 54, 3 25 40, 7 42, 2 53, 1 43, 5 56, 3 58 45, 4 58, 1 60, 3 30 35 61, 2
lindab | we simplify construction Professor Plus Easier handling • The new Professor Plus is equipped with an easy-to-handle faceplate, adapted from our successful Premum and Premax designs.
lindab | we simplify construction Professor or Professor Plus Which one is more suitable? • Professor Plus should be used in situations were the cooling capacity of the original Professor in inadequate. • The original Professor is still very relevant with its low price and low building height. • As the design of the Professor and the Professor Plus beams are identical, both beams can be used in the same project. NEW! For a PLUS on capacity
lindab | we simplify construction Product description A message to the market… • Campaign material will be available on brand. lindab. com – Here you will find examples from a range of different campaigns. The examples contain descriptions, ads, presentations, graphic elements, folders, roll-ups and a lot more. • All product information will be available on lind. QST. com – Description – Product calculator – Related documents § § § Catalogue page Installation instruction Service & maintenance Building product declaration Accessories
we simplify construction