Joint institute for nuclear research The thermometry system

  • Slides: 12
Download presentation
Joint institute for nuclear research The thermometry system of superconducting magnets test bench for

Joint institute for nuclear research The thermometry system of superconducting magnets test bench for the NICA accelerator complex. Volkov V. I. , Gorbachev E. V. , Kirichenko A. E. , Sedykh G. S. NEC’ 2015

Superconducting magnets test bench general view Satellite refrigerators Shoulder 1 NEC’ 2015 Shoulder 2

Superconducting magnets test bench general view Satellite refrigerators Shoulder 1 NEC’ 2015 Shoulder 2 Georgy Sedykh, JINR

Specification - Precise temperature control in the different parts of test bench during cryogenic

Specification - Precise temperature control in the different parts of test bench during cryogenic tests. - The resistance temperature sensors (Pt 100, TVO) are being used as a thermometers. - The quantity of sensors (~25), their location and characteristics depends on type of the test session. The thermometry system should provide: 1. Temperature data acquisition and storage in the 24 x 7 x 365 x 5 mode; 2. Temperature data mapping in the graphs, tables and mnemonic diagrams; 3. Stored temperature data viewing and exporting; 4. Easy configuration; NEC’ 2015 Georgy Sedykh, JINR

Test session thermometry scheme Cryostat with magnet NEC’ 2015 Cryostat with current leads Georgy

Test session thermometry scheme Cryostat with magnet NEC’ 2015 Cryostat with current leads Georgy Sedykh, JINR

Hardware 1. Resistance temperature sensors: - TVO. Range: 1 kΩ (293 K) – 4.

Hardware 1. Resistance temperature sensors: - TVO. Range: 1 kΩ (293 K) – 4. 5 kΩ (4 K); - Pt 100. Range: 100 Ω (293 K) – 7 Ω (4 K); 2. NI PXI-8820 system controller; 3. NI PXIe-4357 Data Acquisition for RTD Measurements (24 bit, 20 channels); 4. Precise current sources - 20 µA for TVO; - 500 µA for Pt 100; Advantages: 1. High precision; 2. High level of interference suppression in 50 Hz; NEC’ 2015 Georgy Sedykh, JINR

Software. Tango device-servers: § ADC data acquisition module (PXI modules control, data acquisition, data

Software. Tango device-servers: § ADC data acquisition module (PXI modules control, data acquisition, data filtering); § Temperature calculation module; § Database storage access module; § System configuration module; § Data export module (Excel, SQL); § Tango modules for web access (REST, Web. Socket, Web. Auth); Advantages: 1. Easy management; 2. Easy extension; 3. Easy implementation to the NICA control system; NEC’ 2015 Georgy Sedykh, JINR

Software. Database § Experiments data storage; § Configuration storage (information about session, sensors, hardware);

Software. Database § Experiments data storage; § Configuration storage (information about session, sensors, hardware); Advantage: • System configuration for the new test session can be performed by the operator through the special configuration tool; NEC’ 2015 Georgy Sedykh, JINR

Software. Client application Web application providing operator interface Advantages: 1. Flexible design (web desktop);

Software. Client application Web application providing operator interface Advantages: 1. Flexible design (web desktop); 2. Access from any device in local network (PC, tablet); 3. No additional software (only web browser); NEC’ 2015 Georgy Sedykh, JINR

Software. Web client application. Table Mnemonic diagram Data viewing NEC’ 2015 Line chart Georgy

Software. Web client application. Table Mnemonic diagram Data viewing NEC’ 2015 Line chart Georgy Sedykh, JINR

Tango web tools § Web. Socket. DS - to read Tango attributes through Web.

Tango web tools § Web. Socket. DS - to read Tango attributes through Web. Sockets; § Rest. DS - to provide access to Tango control system units through http(s) requests (Ajax); § Tango. Web. Auth - to provide web access control; tangodevel. jinr. ru NEC’ 2015 Georgy Sedykh, JINR

Summary: 1. Standalone thermometry system for superconducting magnets test bench; 2. Prototype for the

Summary: 1. Standalone thermometry system for superconducting magnets test bench; 2. Prototype for the NICA thermometry system; 3. Precision of the voltage drop across the sensor measurement ~ 10µV per 80 m. V scale. (~0. 0125%); 4. User-friendly flexible web client application; 5. Toolbox consist of Tango web tools (WS, REST) with Java. Script web framework (like Ext. JS) can be used for developing other control system client applications. Current work: 1. Extend the system to 6 shoulders (currently 2); 2. New powerfull server Supermicro (for data storage); 3. New configuration tool (for operator’s pleasure); NEC’ 2015 Georgy Sedykh, JINR

Thank you for your attention! NEC’ 2015 Georgy Sedykh, JINR