Group Control Wiring Diagram Indoor Unit 2 Indoor

  • Slides: 3
Download presentation
Group Control Wiring Diagram Indoor Unit 2 Indoor Unit 1 Brown(GND) Cassette/Duct Indoor Unit

Group Control Wiring Diagram Indoor Unit 2 Indoor Unit 1 Brown(GND) Cassette/Duct Indoor Unit 16 Yellow (Signal) Main PCB #1 RED Terminal Housing Block(Local supply) Main PCB #2 Main PCB #16 Lead wire Wire of remote controller Jet Cool Temp On/Off Timer Cancel E_Heater Fan Speed Operation Program Week Holiday Set Select Wiring method Air clean Room Temp Auto Swing Hour MIN SET/CLR RESET Wired Remote Controller Components 1. Remove “R 02 K(12 KΩ)”on the Main PCB (Solder side) --See next page 2. Make resister OP 7 open on the PCB in Wired Remote Controller 3. Disconnect the wire of remote controller in indoor unit 1 4. Set up the terminal block 5. Connect the wire of remote controller with terminal, and assemble the housing between main pcb and terminal 6. Connect indoor unit 1& unit 2 with Lead wire(double insulated) 7. Another indoor units(3~16) are also connected like above method 1. Terminal Block, Housing, Lead wire : Local Sourcing 2. But if you want Terminal block and Housing, LG Can provide these optionally.

Remove “R 02 K(12 KΩ)” on the Main PCB (Solder side) Micom chip Slide

Remove “R 02 K(12 KΩ)” on the Main PCB (Solder side) Micom chip Slide s/w for two thermister Slide s/w for Ceiling height OP 7 IC 02 M Micom chip R 02 K Remote Control Board Main PCB Board

Old Version OP 7 Slide Switch (2002. 5. 30)

Old Version OP 7 Slide Switch (2002. 5. 30)