Global Interlock System Design GIS SDR 24 September
Global Interlock System Design GIS SDR 24 September 2009 Scott Bulau
Agenda • 8: 35 - 9: 00 Brief description on ATST (Mark Warner) 9: 00 – 9: 45 Hazard Analysis (Rob Hubbard) 10: 00 – 10: 15 Break 10: 15 – 11: 30 GIS Specifications and Interfaces (Scott Bulau) 11: 30 – 11: 45 Safety Management (Chuck Gessner) 11: 45 – 12: 45 GIS Design (Scott Bulau) 12: 45 – 1: 30 Lunch 1: 30 – 2: 00 GIS Design (cont. ) 2: 00 – 2: 45 Plan of implementation (Scott Bulau) 2: 45 – 3: 00 Break 3: 00 – 4: 30 Executive Session (Committee) Generate Draft Report 4: 30 – 5: 00 Brief Project (Committee) • 5: 00 • • • September 24, 2009 Adjourn ATST GIS SDR 2
General Description • Safety System Only • Distributed System – • each major subsystem, group subsystems/subassemblies Programmable Automation Controllers (PAC) Subsystem Safety Interlocks LIC OCS GIC • Subsystem Controller – – • Global Interlock Controller (GIC) – • Subsystem Safety Interlocks LIC PAC Safety network – – • LIC Safety I/O modules GIS Utilizes safety protocol Certified SIL 3 ESS September 24, 2009 ATST GIS SDR 3
LIC Distribution Distributed System OSS LIC: M 1 motion and thermal, TEOA, GOS, Local Feed Optics • Reduced cabling • Provide subsystems independent configuration and testing • 6 - 7 Local Interlock Controllers (LIC) • 1 Global Interlock Controller (GIC) Mount Base LIC: Altitude Drive Controller , Azimuth Drive Controller, Hydrostatic Bearings Instrument Systems LIC: Wave Front Controller, Science Instruments Coudé Floor LIC: Coudé Drive Controller, Hydrostatic bearings September 24, 2009 ATST GIS SDR 4
TMA LIC Locations September 24, 2009 ATST GIS SDR 5
LIC Distribution cont. Enclosure Thermal LIC: (may be subsumed into Facility or Enclosure LIC) Enclosure LIC: Enclosure Drive Controllers Global Interlock Controller (GIC) Facility LIC: Ground level of operations building September 24, 2009 ATST GIS SDR 6
Network Topology • LICs and GIC – – Safety network Ethernet safety protocol Isolated network Fiber pair, multimode • Safety I/O modules – Subsystem safety network – Ethernet safety protocol – CAT 7, twisted pairs • All the safety I/O are defined in ICD • Provision must be made to add safety I/O • CIP Safety protocol built into safety PACs September 24, 2009 ATST GIS SDR 7
Connectivity to GIS • Interconnects: Ethernet • Protocol: CIP Safety • Tags: major_minor_component_signal e. g. LIC 3_TEOA_heatstop_cover September 24, 2009 ATST GIS SDR 8
Emergency Stop System September 24, 2009 ATST GIS SDR • Current generation e-stop buttons • Hardware independent shutdown of motion controlled devices • GIS monitoring of e-stop – Additional global interlock response – Location • Location and mounting of e-stops as per NFPA 79, Electrical Standard for Industrial Machinery, 10. 7 Devices for Stop and Emergency Stop 9
ATST-DWG-00126 September 24, 2009 ATST GIS SDR 10
Sheet 2 September 24, 2009 ATST GIS SDR 11
E-stop Locations on TMA – – – – September 24, 2009 ATST GIS SDR Sides telescope mount Mount platforms +X, -X M 2 assembly On OSS (near Gregorian focus) Fixed locations on pier, coudé floor Opposite sides mezzanine level Rotator structure, mezzanine level Inside pier at ground level, coudé AZ wrap 12
E-stop Locations on Enclosure & Operations Building Carousel entrance aperture Rear access door, in/out Bridge crane pendant Level access doors +X, -X Upper access platforms TEOA access platform X, Y Shutter drives, back/front Bogie inspection area AZ utility transfer system, front/back – Control room – Instrument prep lab – – – – – September 24, 2009 ATST GIS SDR 13
Compatibility Maintaining compatibility throughout GIS requires specification of both hardware and programming used in subsystems. ATST SPEC-0046 • Specification of the hardware used for the GIC and LIC (1756 Guard. Logix Safety PAC) • • Specification of hardware used by subsystem vendors for safety I/O connection to LIC (1791 ES Guard I/O modules) Specification of the software used in the GIC and LIC (RSLogix 5000) Specification of the software TAGS and use of certified function blocks (TÜV Certified) Communicate on independent safety network (Ethernet/CIP Safety) September 24, 2009 ATST GIS SDR 14
Sample LICs in GIS Ethernet/CIP Safety Guard. Logix Ethernet/CIP Safety Compact Block 8 In / 8 Out Combo BACNET/ Device. Net Compact Block 12 Channel Input Computer (HMI, RSLogix 5000, etc. ) Compact Block 4 Input / 4 Relay Output Standard IP 20 I/O September 24, 2009 ATST GIS SDR Standard IP 67 I/O 15
Commonality • Programmable Automation Controllers (PAC) – – – CLX 4 -slot BP, PS 1756 -L 63 S, 1756 -LSP, CLX based 1756 -ENBT, 1756 EN 2 T/F 8000 Stratix managed switch 1781 ES-IB 12, 1791 ES-IB 4 XOW 4, 1791 ES-IB 8 XOB 8 I/O • Programming of PAC for the GIS: – Producer / Consumer , tag data base system – Ladder Logic programming structure – All safety software shall be developed with RSLogix 5000 in the safety task of the Guard. Logix Controller utilizing current Guard. Logix Safety reference manual # 1756 -rm 093 relative to processor revision. – All safety functions shall be developed in compliance to the Guard. Logix Safety reference manual. September 24, 2009 ATST GIS SDR 16
GIS Configuration September 24, 2009 ATST GIS SDR 17
ICDs • Development of Influence Matrix – ICD 1. 1 -4. 5; Telescope Mount Assembly to GIS – ICD 1. 2 -4. 5; M 1 assembly to GIS – ICD 1. 3 -4. 5; TEOA to GIS – ICD 1. 4 -4. 5; M 2 to GIS – ICD 1. 5 -4. 5; Feed Optics to GIS – ICD 2. 1 -4. 5; Wavefront Correction - Coudé to GIS – ICD 4. 2 -4. 5; Observatory Control System to GIS – ICD 4. 5 -5. 0; GIS to Enclosure – ICD 4. 5 -6. 3; GIS to Facility Equipment – ICD 4. 5 -6. 6; GIS to Interconnects September 24, 2009 ATST GIS SDR 18
Global Interlock System Reference Design - END - September 24, 2009 ATST GIS SDR 19
- Slides: 19