ECE 476 POWER SYSTEM ANALYSIS Lecture 23 Transient

  • Slides: 34
Download presentation
ECE 476 POWER SYSTEM ANALYSIS Lecture 23 Transient Stability Professor Tom Overbye Department of

ECE 476 POWER SYSTEM ANALYSIS Lecture 23 Transient Stability Professor Tom Overbye Department of Electrical and Computer Engineering

Announcements l l l Be reading Chapter 11 and Chapter 12 thru 12. 3

Announcements l l l Be reading Chapter 11 and Chapter 12 thru 12. 3 HW 10 is 11. 4, 11. 7, 11. 10, 11. 19, 11. 20; due Dec 1 in class. Project is due Thursday Dec 1 in class. 1

Power System Time Scales Lightning Propagation Switching Surges Stator Transients and Subsynchronous Resonance Transient

Power System Time Scales Lightning Propagation Switching Surges Stator Transients and Subsynchronous Resonance Transient Stability Governor and Load Frequency Control Boiler/Long-Term Dynamics Voltage Stability Power Flow 10 -7 10 -5 10 -3 0. 1 10 Time (Seconds) 103 105 Image source: P. W. Sauer, M. A. Pai, Power System Dynamics and Stability, 1997, Fig 1. 2, modified 2

Power Grid Disturbance Example Figures show the frequency change as a result of the

Power Grid Disturbance Example Figures show the frequency change as a result of the sudden loss of a large amount of generation in the Southern WECC Green is bus quite close to location of generator trip while blue and red are Alberta buses. Black is BPA. Time in Seconds Frequency Contour 3

Frequency Response for Gen. Loss • In response to rapid loss of generation, in

Frequency Response for Gen. Loss • In response to rapid loss of generation, in the initial seconds the system frequency will decrease as energy stored in the rotating masses is transformed into electric energy • • Solar PV has no inertia, and for most new wind turbines the inertia is not seen by the system Within seconds governors respond, increasing power output of controllable generation • Solar PV and wind are usually operated at maximum power so they have no reserves to contribute 4

Generator Electrical Model l The simplest generator model, known as the classical model, treats

Generator Electrical Model l The simplest generator model, known as the classical model, treats the generator as a voltage source behind the direct-axis transient reactance; the voltage magnitude is fixed, but its angle changes according to the mechanical dynamics 5

Generator Mechanical Model Generator Mechanical Block Diagram 6

Generator Mechanical Model Generator Mechanical Block Diagram 6

Generator Mechanical Model, cont’d 7

Generator Mechanical Model, cont’d 7

Generator Mechanical Model, cont’d 8

Generator Mechanical Model, cont’d 8

Generator Mechanical Model, cont’d 9

Generator Mechanical Model, cont’d 9

Generator Swing Equation 10

Generator Swing Equation 10

Single Machine Infinite Bus (SMIB) l To understand the transient stability problem we’ll first

Single Machine Infinite Bus (SMIB) l To understand the transient stability problem we’ll first consider the case of a single machine (generator) connected to a power system bus with a fixed voltage magnitude and angle (known as an infinite bus) through a transmission line with impedance j. XL 11

SMIB, cont’d 12

SMIB, cont’d 12

SMIB Equilibrium Points 13

SMIB Equilibrium Points 13

Transient Stability Analysis l 1. 2. 3. For transient stability analysis we need to

Transient Stability Analysis l 1. 2. 3. For transient stability analysis we need to consider three systems Prefault - before the fault occurs the system is assumed to be at an equilibrium point Faulted - the fault changes the system equations, moving the system away from its equilibrium point Postfault - after fault is cleared the system hopefully returns to a new operating point 14

Transient Stability Solution Methods l 1. There are two methods for solving the transient

Transient Stability Solution Methods l 1. There are two methods for solving the transient stability problem Numerical integration l 2. this is by far the most common technique, particularly for large systems; during the fault and after the fault the power system differential equations are solved using numerical methods Direct or energy methods; for a two bus system this method is known as the equal area criteria l mostly used to provide an intuitive insight into the transient stability problem 15

SMIB Example l Assume a generator is supplying power to an infinite bus through

SMIB Example l Assume a generator is supplying power to an infinite bus through two parallel transmission lines. Then a balanced three phase fault occurs at the terminal of one of the lines. The fault is cleared by the opening of this line’s circuit breakers. 16

SMIB Example, cont’d Simplified prefault system 17

SMIB Example, cont’d Simplified prefault system 17

SMIB Example, Faulted System During the fault the system changes The equivalent system during

SMIB Example, Faulted System During the fault the system changes The equivalent system during the fault is then During this fault no power can be transferred from the generator to the system 18

SMIB Example, Post Fault System After the fault the system again changes The equivalent

SMIB Example, Post Fault System After the fault the system again changes The equivalent system after the fault is then 19

SMIB Example, Dynamics 20

SMIB Example, Dynamics 20

Transient Stability Solution Methods l 1. There are two methods for solving the transient

Transient Stability Solution Methods l 1. There are two methods for solving the transient stability problem Numerical integration l 2. this is by far the most common technique, particularly for large systems; during the fault and after the fault the power system differential equations are solved using numerical methods Direct or energy methods; for a two bus system this method is known as the equal area criteria l mostly used to provide an intuitive insight into the transient stability problem 21

Transient Stability Analysis • 1. 2. 3. For transient stability analysis we need to

Transient Stability Analysis • 1. 2. 3. For transient stability analysis we need to consider three systems Prefault - before the fault occurs the system is assumed to be at an equilibrium point Faulted - the fault changes the system equations, moving the system away from its equilibrium point Postfault - after fault is cleared the system hopefully returns to a new operating point 22

Transient Stability Solution Methods • 1. There are two methods for solving the transient

Transient Stability Solution Methods • 1. There are two methods for solving the transient stability problem Numerical integration l 2. this is by far the most common technique, particularly for large systems; during the fault and after the fault the power system differential equations are solved using numerical methods Direct or energy methods; for a two bus system this method is known as the equal area criteria l mostly used to provide an intuitive insight into the transient stability problem 23

Numerical Integration of DEs 24

Numerical Integration of DEs 24

Examples 25

Examples 25

Euler’s Method 26

Euler’s Method 26

Euler’s Method Algorithm 27

Euler’s Method Algorithm 27

Euler’s Method Example 1 28

Euler’s Method Example 1 28

Euler’s Method Example 1, cont’d t xactual(t) x(t) Dt=0. 1 x(t) Dt=0. 05 0

Euler’s Method Example 1, cont’d t xactual(t) x(t) Dt=0. 1 x(t) Dt=0. 05 0 10 10 10 0. 1 9. 048 9 9. 02 0. 2 8. 187 8. 10 8. 15 0. 3 7. 408 7. 29 7. 35 … … 1. 0 3. 678 3. 49 3. 58 … … 2. 0 1. 353 1. 22 1. 29 29

Euler’s Method Example 2 30

Euler’s Method Example 2 30

Euler's Method Example 2, cont'd 31

Euler's Method Example 2, cont'd 31

Euler's Method Example 2, cont'd x 1 actual(t) x 1(t) Dt=0. 25 0 1

Euler's Method Example 2, cont'd x 1 actual(t) x 1(t) Dt=0. 25 0 1 1 0. 25 0. 9689 1 0. 50 0. 8776 0. 9375 0. 7317 0. 8125 1. 00 0. 5403 0. 6289 … … … 10. 0 -0. 8391 -3. 129 100. 0 0. 8623 -151, 983 t 32

Euler's Method Example 2, cont'd Below is a comparison of the solution values for

Euler's Method Example 2, cont'd Below is a comparison of the solution values for x 1(t) at time t = 10 seconds Dt x 1(10) actual -0. 8391 0. 25 -3. 129 0. 10 -1. 4088 0. 01 -0. 8823 0. 001 -0. 8423 33