Eaton arc flash relay system 2016 Eaton All












- Slides: 12

Eaton arc flash relay system © 2016 Eaton. All rights reserved.

Arc faults • Most devastating type of fault in MV and LV electrical assemblies • Current flow through ionized air—> plasma • Most arc faults are caused by human errors • 80% of arc faults start in the cable compartment • A single-phase arc fault develops quickly into a three-phase low impedance high power arc fault © 2016 Eaton. All rights reserved. 2

Eaton arc flash relay system • The Eaton arc flash relay (EAFR) system is a combination of arc flash relay modules and sensors designed to detect and clear arc flash events in low- and medium-voltage electrical assemblies © 2016 Eaton. All rights reserved. 3

Arc fault protection philosophy • Speed—no intentional delays • Less than 2 ms relay operate time • Sensitive • Current set-points just above loads, sensitive ground-fault set points • Selectivity • Trip-only affected feeder(s) • Secure—dual-sensing prevents false trips • Phase and ground instantaneous overcurrent elements act as a permissive for the light sensing inputs • Self monitoring • System monitors all internal system functions along with external connections between modules, light sensors or loops and current transformers © 2016 Eaton. All rights reserved. 4

Eaton arc flash relay modules Features EAFR-110 F EAFR-110 P EAFR-102 EAFR-101/D Three-phase current detection Yes No No Ground current detection Yes No No Maximum point sensors 0 12 Maximum fiber loop sensors 3 0 High-speed outputs (2 ms) 2 2 0 0 Trip relays (7 ms) 4 4 EAFR-110 EAFR-101/102 EAFR-101 D © 2016 Eaton. All rights reserved. 5

EAFR-01 point sensor • Point sensor in each enclosed compartment and every 3 feet in open areas • Sensor cable—shielded twisted pair 18 -20 AWG • 3 wire (+24 Vdc, signal, Gnd) • Current based information (2 m. A, 20 m. A) • Self monitoring verifies correct field connections • Maximum 3 sensors in line (up to 328 feet) © 2016 Eaton. All rights reserved. 6

Factory Installed Point Sensors (single ended) Selective Breaker Trip Non – Selective Breaker Trip © 2016 Eaton. All rights reserved. 7

Factory Installed Point Sensors (double ended) Non – Selective Breaker Trip © 2016 Eaton. All rights reserved. 8

Fiber sensors Fiber type Plastic (EAFR-06) Glass (EAFR-07) High-temp glass (EAFR-08) Light intensity threshold 8000 lux Detection radius 360 degrees Max length 40 m (131 ft) 50 m (164 ft) Diameter 1 mm (0. 039 in) 1. 2 mm (0. 047 in) Bending radius 5 cm (2 in) 1 cm (0. 394 in) Operating temperature -10 to 85°C -40 to 125°C © 2016 Eaton. All rights reserved. 9

Fiber Loop Retrofit © 2016 Eaton. All rights reserved. 10

Provides safety and efficiency in various applications Oil and gas Commercial or institutional infrastructure Industrial Electric utilities © 2016 Eaton. All rights reserved. 11

Thank you © 2016 Eaton. All rights reserved.
Eaton arc flash relay
Dorothy eaton watts
Frame relay and atm
Digital photography with flash and no-flash image pairs
Cat 2 arc flash ppe
Arc flash ppt
Construction safety association of ontario
Eddie adams arc flash
Arc promoteur vs arc investigateur
Minor arc and major arc
Major arc
Arc emu88 com arc info 09 100009 html
Name a line containing point a