Autro Safe Self Verify Interactive Fire Gas Detection































- Slides: 31
Autro. Safe Self. Verify Interactive Fire & Gas Detection System ID: ASAFE_intro_Eng, 2007 -09 ID: 1
Overview and a brief introduction of; § § § § § Reference to traditional systems The Autro. Safe system Background for development – IEC EN 54 Autro. Safe terminology Features introduction Self. Verify System Integrity (SIL) Reliability Communication Software Tools ID: 2
Traditional Analogue Addressable Fire-Alarm Systems BU-100 5 th Deck BU-70 4 th Deck BU-100 3 rd Deck BU-70 2 nd Deck BU-100 BRANN LER CCR 1 st Deck Utility Deck DYNAMIC FILTER PROCESS ID: 3
Autro. Safe Self. Verify Interactive Fire-& Gas Detection System 5 th deck Corridor LER Corridor 4 th deck LER Corridor 3 rd deck LER Corridor 2 nd deck LER CCR LER 1 st deck Utility-deck ID: AUTROLON 4
Traditional F & G System Autro. Safe DCS system Operator Station Standard Loop Units Node 1 Redundant Network Node 2 Node 3 Node 4 Node 5 Node 6 EX Loop Units Autro. Point Autro. Flame Third party detectors Simrad ID: Autro. Path HC 600 RX Autro. Path HC 600 TX Kidde Fenwal Analaser II Autro. Flame CCTV 5
Autro. Safe Panel (TCP/IP) Autro. Safe IFG Autro. OS Autro. Safe Panel Mod. Bus To Process Control System Autro. Safe Controller Al_Com loop Autro. LON Standard Autro. Safe loop units Information/ Repeater panel Barrier unit BZ-500 BSD-340 Autro. Field. Bus Autro. Safe EX loop units BSD-321 Autro. Flame X 33/1 PL Power. Loop Video BN-342 (4 -20 m. A) Third-party Detector Kidde Fenwal Analaser II Autro. Path HC 600 Autro. Flame CCTV ID: 6
Autro. Safe and EN 54 § Autro. Safe: Developed and approved in accordance with EN 54 -2 and EN 54 -4 § Autro. Safe: Considers the demands of future EN 54 norms § Autro. Safe: Exploits all the possibilities of EN 54 (American equivalent is NFPA 72 – Autro. Safe is also FM approved – thus tested and approved against NFPA 72) ID: 7
Features, Performance, Functionality. . § § § § ID: Interactive loop Communication Automatic addressing Intelligent field devices Increased reliability – key terms: § Self. Verify TM § DYFI+ (Dynamic Filter Process) Built-in Short circuit isolators Loop topology Fail-safe loop communication Roughed loop communication 8
Terminology – mostly based on EN 54 Some examples: DECK 3, CORRIDOR Heat Detector DECK 3, LER SOUTH Smoke Detector Operator panel DZ-2 DZ-1 F W R E A A F K K A 2 1 R E DZ-3 OZ-1 CCR Optical Smoke Detector AZ-2 = DZ: Detection zone = AZ: Alarm zone AZ-1 DZ-4 WORKSHOP Multi-sensor Detector AZ-3 = OZ: Operation zone ID: 9
Autro. Safe Self. Verify System Panels Maximum flexibility: Easy to read, understand operate Fire & Gas Alarm panel Operator Panel Repeater Panel Information Panel Controller ID: 10
Autro. LON § Autro. Safe panels in a Ring loop § Short-circuit isolators in every panel – all panels will continue to operate even with a single break or short circuit on the Autro. LON § Maximum 32 panels in one LONring (but needs a Booster for each 8 th panel) § Fibre-optic modems available (3000 meters between two panels) Back to main page. ID: 11
Autro. Safe Panel § § A complete fire and gas control panel with full operator capabilities Supports up to 6 fire detection loops and 1 Autro. Field. Bus 2 Autro. Com Serial, 1 Autro. Com Ethernet (TCP/IP) Outputs and inputs, monitored or unmonitored Back to main page. ID: 12
Autro. Safe Controller § § § Serves as a connection unit for detection loops (maximum 6) 1 Autro. Field. Bus 2 Autro. Com Serial, 1 Autro. Com Ethernet Outputs and inputs, monitored or unmonitored Communicates with other system units on AUTROLON Back to main page. ID: 13
Autro. Safe Information/ Repeater Panel Information Panel § Serves as an indication device only § Provides information related to the defined operation zone(s). Repeater Panel § Displays alarms and allows operation of alarms and receipt of additional information related to the relevant operation zone Back to main page. ID: 14
Autro. Safe Self. Verify, a Modular System A variety of DIN rail mounted I/O modules available. . • Loop drivers • Digital output modules • 24 V alarm output modules • Digital input modules ID: 15
A Wide Range of Products for All Applications Series Units Heat detectors Optical smoke detectors High-sensitivity Multisensor smoke detectors Manual Call-points Interface/ address units Sounder Series 200 Standard Interactive. Addressable units Series 300 With Self. Verify® functions Series 500 With special protection for marine, offshore, Exi applications ID: 16
AL_Com Loop § Ring loop-topology with detectors, I/O interfaces and sounders § Short-circuit isolators in every loop unit – all detectors and interfaces will continue to operate even with a single break or short circuit on the AL_Com Loop § One branch between two units on the main loop § All ‘decisions’ made by loop unit, event messages sent to panel § Fail-safe operation if communication fails. Back to main page. ID: 17
Standard Autro. Safe Loop Units § § The detection loop is connected directly to the Loop Driver Module All types and series of Autro. Safe detectors, manual call-points and I/O units can be connected to the same detection loop (99 det/mcp + 27 I/O) Back to main page. ID: 18
Autro. Safe EX Loop § § § Connected to one barrier (branch) between two units on the main loop Maximum 20 EX-units on one branch Most Autronica-detectors and I/Ounits are produced in EX-versions Back to main page. ID: 19
Large Assortment of I/O Units A number of loop controls and Interface units are available § § § Disablement input-units Interface units for alarm and faults Door control and monitoring units Output control unit General monitoring and control units Sprinkler monitoring units ID: 20
BSL-330/X § § § Interfaces on-site third-party systems The following messages can be transmitted (from/to an Autro. Safe fire -alarm panel): § fire alarms § pre-alarms § faults § technical alarms from I/O units and event handling from thirdparty devices Four different versions Back to main page. ID: Version Modbus Port 2 BSL-330/1 Slave RS-422/RS-485 BSL-330/2 Master RS-422/RS-485 BSL-330/3 Slave RS-232 BSL-330/4 Master RS-232 33
Autro. Com directly to DCS § § § ABB AC 400 ABB AC 800 Siemens Kongsberg Emerson Hima Advantages of direct communication and propriatary protocol: Fuctionality and SIL! ID: 34
Autro. OS § § A remote monitoring and control system that enables full operation of the Autro. Safe fire-alarm panels All alarms, faults, inhibits, overrides and outputs can be monitored and controlled from the Autro. OS stations Video from CCTV flame cameras Microsoft Windows platform Back to main page. ID: 35
Autro. Safe Sys. & Utility Software Package § AS Configuration Tool § § Merge Tool Power Calculators Import/Export Tools Download Tools § AS I/O Simulator Tool § The perfect Application Software verification Tool § Loop Diagnostics Tool § WAS-2000 and AS-2000 ID: 36
What is Self. Verify®? Self. Verify® function: The detectors are tested once every 24 hours with a calibrated signal ID: 37
Standard Analogue Addressable Fire-Alarm System Supply Power supply Detector Loop Communication interface Monitored parts Non. Calibrated test Smoke detector Fault Warning warning Fault Signal signal Fault ALARM! Fire Alarm signal Fire Alarm Signal STOP! Operation Alarm signal ID: Detector test with test gas Detector smoke chamber 39
Self. Verify® Fail-safe detectors give increased reliability, and reduce maintenance costs dramatically Power supply Communicationinterface SVcontrol Smoke detector Fault warning Fault signal ALARM! Fire Alarm Signal STOP! Operating Alarmsignal Self. Verify® stimulator Detector smoke chamber Calibrated test Monitored part ID: 40
Why Self. Verify®? Self. Verify® – Reduces the need for manual testing is significantly ID: 41
System Integrity § R&D target for System Integrity: No single fault shall degrade system performance § SIL 2 (Safety Integrity Level 2) in accordance with IEC-61508 (By TÛV and NEMCO) ID: 42
SIL 2 Certificates by TÛV and NEMCO ID: 43
Comprehensive list of Approvals § § § § American Bureau of Shipping ATEX (NEMCO) Bosec BUREAU VERITAS AND AUTORITES MARITIMÈS FRANCAISES China Compulsory Certification China Classification Society China National Quality Supervision and test centre for explosion protected electrical products Dansk brand- og Sikringsteknisk Institut Det Norske Veritas (DNV) Forsikringsselskapenes Godkjenningsnevnd FM APPROVALS Germanischer Lloyd Japanese Government Lloyd's Register of Shipping ID: § § § § § Maritime and Coastguard Agency Nonprofit Independent Research Organisation “Certification Centre of Explosion-proof and Mine Electrical Equipment" - Nanio “CCVE" Nippon Kaiji Kyokai Polski rejestr Statków Registro Italiano Navale Russian Maritime register of Shipping Svensk Brand- och Säkerhets Certifiering ab United States Coast Guard Vniipo/Gost 44