ACAlarms Description Alarms to be transmitted Ac Fail
A/C+Alarms Description Alarms to be transmitted Ac Fail High Temp DC pri Alarm DC sec Alarm Rectifier Fail Air/Cond Fail Door Open Smoke Temp Relay 24 V Air/Cond 1 4 p +1 Power socket ENT/EX 40 A for Gen – 48 VDC Power supply Gen R Gen S DC pri Alarm DC sec Alarm Rectifier Fail Battery Disch Relay 24 V LVDB off Gen T ON OFF POWER ALARM High Temp Tank Alarm Relay 24 V Air/Cond 2 – 48 VDC Power supply Ac Fail Gen Set Temp Int. Det Temp Ex. Det DC Extractor Battery Disch Relay 24 V DC extractor Air/Cond Fail Gen Set Tank Alarm Door Open Smoke Temp Alarms to be received Protek Telecom&Electronics Confidential. [For internal and NDA customers]
Shelter System Block Biagram Temp. det. 2 Gen. Set (external) AIR COND 1 AIR COND 2 Temp. det. 1 AC CONTROL Rectifier BATT set ALARM & TRANSMISSION CONTROL SYSTEM DDF/ MDF LVDB Door sensor Fire det Smoke det. AIR EXTRACTOR Protek Telecom&Electronics Confidential. [For internal and NDA customers]
A/C Control +Alarms General Specifications USER INTERFACE * MENU DRIVEN SYSTEM * 2 LINE ALPHANUMERIC DISPLAY * CONTROL KEYS * LED INDICATORS GENERAL I/O SYSTEM * All dry contact I/O system (15 i/p, 15 o/p, 1 o/p main Ac cut-off, 1 o/p Air/Cond 1 on-off, 1 o/p Air/Cond 2 on-off). * Each I/O can be separately defined as N. O. or N. C… * Power feeding for external sensors (5 V) * 6 analogue inputs for sensors outputs evaluations (temperature, etc. ) GENERAL FACILITIES * Flexible I/O definition: Each I/O connection can be assigned to any I/O type during installation. * Time based outputs : Outputs can be activated on timeely by user programming. * Configuration program from a reference system Protek Telecom&Electronics Confidential. [For internal and NDA customers]
A/C Control +Alarms General Specifications CONTROLLED INPUTS AND OUTPUTS INPUTS 1. Door open 2. High temperature 3. Temperature 4. Smoke 5. Fire 6. AC mains fail 7. DC Primary 8. DC Secondary 8. Rectifier Fail 9. Battery discharge 10. Air conditioner fail 11. Genset activated 12. Genset tank OUTPUTS 1. Alarm outputs to be defined by user for any of the states above negating the normal conditions. 2. Controllable outputs: *Timing operation of air conditioners, *Alarm logic controlled of main power cutoff due to fire alarm case activation. Protek Telecom&Electronics Confidential. [For internal and NDA customers]
Menu System * Use scroll keys to go to any menu item * Use key to go to sub menu items/key to go up from existing menu * Use scroll keys to go to any menu item * Use ENTER key to select any item Scrolling using up and down keys, a * sign appears on the related item. POWER ON: Following main menu appears *PASSWORD FACT. SETTINGS CONFIGURE START Press key to continue *PASSWORD + ENTER : Allows user to define a new password. Enter 4 digit password => screen: **** then ENTER. *FACT. SETTINGS *CONFIGURE : Factory settings of Temperature / Timer functions are confirm : Factory settings of Temperature / Timer functions are as; Use keys to scroll the list. *T 1 temperature for Air Cond. 1 *T 2 temperature for Air Cond. 2 *T 3 temperature for Air Extracter *Timer 1 for Air Cond 1 on time. *Timer 2 for Air Cond 2 on time. *AC contactor off logic ( as Default logic: fire, smoke, . . . ) *Urgent Alarm configuration from alarms *Non urgent configuration from alarms Protek Telecom&Electronics Confidential. [For internal and NDA customers]
Menu System *CONFIGURE : Use to configure the states and function of the I/O ports. Use key to select CONFIGURE. Following menu appears. Protek Telecom&Electronics Confidential. [For internal and NDA customers]
Working Display Example Shelter temperature 25 o. C Air Cond 1 active, remaining time 2 h Non urgent alarm (Default) Mains fail, DC primary, DC secondary, Rectifier fail, Door open, Aircond. fail Urgent alarm (Default) Fire, Smoke, High Temperature, Tank level Gen actived, Battery discharged Protek Telecom&Electronics Confidential. [For internal and NDA customers]