A Specifier’s View of DALI June 4, 2002 4: 00 PM Seminar #18 Richard Miller, PE, LC Hellmuth, Obata + Kassabaum, Inc. Sponsored by The International Association of Lighting Designers Sponsored by The Illuminating Engineering Society of North America Produced and Managed by AMC, Inc. Official On-Site Event Directory
DALI Digital Addressable Lighting Interface • “DALI is a protocol dedicated purely for lighting control” • DALI allows individual control and monitoring of lighting systems • DALI provides precise dimming • DALI promises flexibility in design, and ease of installation
Learn How To: • Leverage the benefits of the DALI technology • Specify DALI lighting controls • Design DALI controls for single rooms, open offices and whole buildings • Solve DALI installation and commissioning issues
Current Lighting Control Systems – – – Agili-T by Lightolier Centura by Leviton Digital-Micro. Watt by Lutron DMX 512 by USITT Easylite by Easylite Ballasts and Lighting Systems Ergolight by Ledalite GR 2400 by Lighting Control and Design IBECS by Lawrence Berkeley National Lab Nex. Light by Northpoint Engineering Co. Power. Link by Square D Company Super. Dim by Energy Savings Inc Synergy by Lithonia
Current Wiring for Conference Room
History: From Europe • Tridonic and others – Digital Serial Interface (DSI) ballasts in 1991 – Digital Addressable Lighting Interface (DALI) ballast in 1998 – Dropped royalties to gain wide spread acceptance of DALI • IEC – DALI protocol (IEC Standard 60929, Annex E & G) advanced to voting process in year 2000. – Adopted by other leading ballast and control manufactures – Formally adopted summer of 2002
History: In USA • NEMA Controls Council – Wiring Devices, Controls, and Ballasts – Liaison with International Electrotechnical Commission (IEC) – DALI subcommittee • IESNA Controls Subcommittee – Established to develop a control protocol – Reviewed several existing systems – Asked by NEMA to comment on DALI proposal
DALI AG • Promote the DALI protocol • Review protocol compliance by manufactures • 24 members as of September 2001 – – – International Rectifier, CA Lightolier, Canada Lutron, PA Osram, Germany Philips, Netherlands Tridonic, Austria • (www. DALI-AG. org)
Benefits • Lower initial cost to the Owner – Simple wiring • Higher level of maintenance to the Facility Manager – Status of lamp and ballast • Greater flexibility to the Lighting Designer – Change grouping via software • Lower energy costs to the User – Reduced power consumption • Greater sense of control to the Occupant – Individual control
DALI • DALI is not a product • DALI is a protocol (a set of rules) (from ballast perspective) – Power connection – Lamp response – Control interface – Command set
Protocol: Power Connection • Initial application of voltage – lamps go to full output or other preset level • Universal voltage input – 115 V to 300 V, 50 Hz to 60 Hz • High power factor • Low harmonics • Transient protection
Protocol: Lamp Response – Precise dimming curve • Logarithmic curve • Range: 0. 1% to 100% for incandescent, 1% to 100% for linear fluorescent, 3% to 100% for CF • 254 steps (2. 8% increase per step) • Based on lamp arc power • (This is not lamp lumen output)
Protocol: Control Interface • • • Intent Electrical Media Wiring Bits and Bytes No Collision Detection
Control Interface: Intent • Low cost • Simple • Low interference • Interchangeable
Control Interface: Electrical • Voltage – 0 VDC (+/- 4. 5 V) to 16 VDC (9. 5 V to 22. 5 V) • Voltage drop – must not exceed 2 volts • Loss of control voltage – lamps go to preset level • Current – 2 ma consumption, able to sink 250 ma • Power – Remote power supply of <250 ma • Speed – 1, 200 bits/sec (compare to Ethernet at 100 Mb/s) • Must be able to withstand live voltage
DALI Ballast Block Diagram
Control Interface: Media • • • Two wire Twisted pair not required Shielded pair not required Non-polarized No End-of-Line resistor Standard building wire
Single DALI Loop Diagram PCA EXCEL one 4 all Digital bus Bus. Master Computer User IR Receiver PIR Interface wall switch Interface DALI-PS
Control Interface: Wiring • Maximum length of 300 meters • Open topology: chain, star, tree • Class 2 (may be wired as Class 1) (for ballasts, controls? ) • May be installed with line voltage
DALI Wiring Topology Diagram Serial Connection Star Connection
Control Interface: Bits and Bytes • Address (one specific ballast) • 0 AAAAAA 1 + CCCC , 0 AAAAAA 0 + arc power • Broadcast (all ballasts) • 1111 + CCCC , 11111110 + arc power • Group • 100 GGGG 1 + CCCC , 100 GGGG 0 + arc power • “Go To Scene”: • 0 AAAAAA 1 + 0001 SSSS • 1111 + 0001 SSSS • 100 GGGG 1 + 0001 SSSS
Control Interface: No Collision Detection • Assumes only one sending device • Ballasts talk only when queried • No checking for simultaneous commands • Control manufacturers must provide collision detection
Protocol: Command Set • Current command set is for ballasts only. • >100 commands defined (with space for future commands) • Ability to program, control and monitor status information
Ballast Commands: To Ballast – – – Off Step Up Step Down, On and Step Up Set Max Step Down and Off Set Min Go to Max Go to Min Up to Max Down to Min – – – Fade to Level Set Actual Level Set Power On Level Set System Failure Level Set Fade Time Set Fade Rate Set Scene Go to Scene Remove from Scene Set Group Remove from Group
Ballast Commands: Information from Ballast (Query) – – – Actual Level, Power ON Level System Failure Level Max Min Group Assignment – – – Scene Level Fade Time Random Address Version Number Device Type
Device Types – Type 0 – Standard (fluorescent) – Type 1 – Emergency lighting – Type 2 – HID lamps – Type 3 – Low voltage halogen lamps – Type 4 – Line voltage incandescent lamps – Type 5… 255 – Future device types
DALI Programming • Each DALI loop can support up to 64 individual addresses • When in initial programming mode: • Each ballast generates a 24 bit random address • Control unit then assigns a 6 bit short address (0 to 63) to each ballast • May reassign a 6 bit address to each ballast • May assign a 6 bit address by disconnecting a lamp from the ballast
DALI Programming (Cont’d) • Group Addressing – Each DALI loop can support up to 16 individual groups – Each ballast may belong to any or all of the 16 available groups • Scene Setting – Each ballast may have as many as 16 preset levels (scenes) – Scenes may be applied to ballasts – Scenes may be applied to groups
Wiring per NEC • Approved for use in Class 1 and Class 2 installations • DALI wiring may be with line-voltage wiring • Could use a 5 -wire prefabricated wiring assemble • Installation must comply with Code • Verify rating of control units
Electrician’s Wiring Diagram
Auxiliary Components • Power Supply – Voltage – 16 VDC (9. 5 V to 22. 5 V) – Power – <250 ma • Controller Units – Scene Controller – Daylight Harvesting Controller – Occupancy Controller • Computer Interface (optional)
Sensor Connection Diagrams To Control Unit To DALI Loop
Auxiliary Components (Cont’d) • Gateways – DALI – RS 232 – DALI - Ethernet – RS 232 – Ethernet hub – In separate cabinet from the branch circuit panelboard
Busmaster Enclosure Installation RS 232 Connection
Panelboard and Busmaster Cabinet
Complete Building Control
Next Generation Technology
Palm Pilot Interface Select groups dim up and down Off Select light scenes
User Interface
Protocol – Intent: Interchangeability • Manufactures: web site (DALI-AG. org) • DALI protocol is the minimum requirement – Provides compatibility among manufacturers • Proprietary features are not prohibited – DSI – Line-voltage control
Designing Control Systems • Lighting Plan for Typical Office • Lighting Plan for Conference Room
Lighting Plan for Open Office – CEC Title 24: mandatory • • Two level or dimming Occupancy / Auto Off Daylight Harvest Time-of-Day off with timed manual override – Adjust for individual comfort – Weekend function – Security function – Power reduction
STEP 1: Design fixture layout or retrofit existing fixtures with DALI compatible ballast.
STEP 2: Layout DALI network (2 wires) to each fixture independent of circuit wiring. Each DALI loop can support up to 64 ballast. Loop wires can be located in same conduit with power wiring
STEP 3: Design controls into space and determine easiest connection to DALI bus. Identify placement of bus power supply and optional network interface.
STEP 4: Address DALI ballasts. Determine fixture groupings and map control devices to fixtures. Each ballast can be assigned to multiple groups (16 max).
Network System Configuration LP
Lighting Plan for Conference Room • Multiple luminaries for multiple functions • Multiple preset scenes • Manual controls
Conference Room Lighting Plan
Commissioning • • • DALI Ballast Manufacturer DALI Controller Manufacturer Luminaire Manufacturer Architect Lighting Designer Electrical Engineer Electrician Manufacturer’s Representative Programmer Systems Integrator Commissioner
Commissioning: • DALI Product Manufacturer – Test product prior to shipment • Luminaire Manufacturer – Test assembly prior to shipment – Could preprogram addresses, groups, scenes • Electrician – – Require high quality splices and terminations Document power wiring and control wiring Verify power wiring and lamping Verify DALI loop – broadcast raise/lower, count ballast quantity
Commissioning: (Cont’d) • Lighting Designer / Electrical Engineer – Determine preset levels for scenes • Programmer – Assign and document groups – Assign and document scenes • Systems Integrator – Combine with IT or AV?
Commissioning: (Cont’d) • Manufacturer’s Representative – May be the Commissioner • Commissioner – – – Two people with walkie-talkies Document groupings Flash addressed ballast until that ballast is found Cycle through addresses to find ballast address Document ballast addresses on lighting plans
Benefits of DALI • • • Simplify wiring installation Decrease energy usage Lower maintenance cost Increase space flexibility Improve occupant comfort
Limitations of DALI • Command Set • Fade Time: <0. 7 sec to 90 sec • Requires computer to initialize and program • Intended only for lighting • Not enough products
Wish List • • Compact Fluorescent Ballast Incandescent Dimmer – 120 Volts Incandescent Dimmer – 12 Volts Metal Halide Ballast LED Driver Occupancy Sensor Photo Sensor Daylight Harvesting
Wish List (Cont’d) • • Schedulers Peak Load Shaving Audio/Visual Interface Motor Control for Blinds, Curtains, Projection Screens • Gateways for BACnet®, DMX 512, LONWORKS®, and TCP/IP • Interface to 0 -10 V dimming system
Credits • • • • Dalai Lama Ian Ashdown Bob Beatty Brian Beck Dick Brecher Pekka Hakkarainen Gregg Hauser Wayne Morrow Dave Peterson Steve Purdy Nehal Shah Howard Yaphe Kayo Shibano • • Advance / Philips DALI-AG Leviton Lightolier Osram Sylvania Star. Field Controls Tridonic The Watt Stopper
Conclusion • • My original premise Discoveries Not enough products “Sustainable Competitive Advantage”
HELLO DALI
- Access specifiers in java
- What is inheritance in c++
- Anatomy chest x ray
- Name
- Front view top view
- Simple view and complex view
- Revolved sectioning
- Component of operating systems
- Isometric view and isometric projection
- Isometric drawing
- Simple view and complex view
- Section example
- Separatist view of business ethics
- For the view create view instructor_info as
- For the view create view instructor_info as
- The top view is directly above the right side view
- @html partial
- Birds eye view vs worm's eye view
- Multi-view projection
- Simple view and complex view
- Revolve section view
- Pull supply chain
- Dali algorithm
- Salvadod dali
- Salvador dali narcis
- Instituto interamericano salvador dali
- Salvador dali nacio
- Dali slave market
- Mona lisa golden ratio
- Salvador dalí young
- Mapa conceitual surrealismo
- Irrational number
- Salvador dali art movement
- Exquisite corpse dali
- Kenmerken van surrealisme
- Ies salvador dali leganes
- Vak kiinteistöautomaatio
- Gl parotidea innervasyonu
- Afirmao
- Topologie dali
- Automatismo psichico significato
- Dadaizm ubu imperator
- Dal i
- Muchacha en la ventana salvador dali
- Los relojes de dali
- Biografia w prezentacji
- Elsa schiaparelli e salvador dali
- Salvador dali nacio en
- Las meninas período
- Pnecu
- Where was salvador dali born
- Apparizione di un volto e di una fruttiera sulla spiaggia
- El grito
- Dr jacek pieta
- Autoportrait mou de salvador dali
- Characteristics of surrealism
- Max ernst
- Nervus ophthalmicus dalları
- Alpay çeliker
- Tilted arc
- Subcostales